Download Print this page

Electrolux KSV26HRC Diagnostic Manual page 24

Split system air conditioner
Hide thumbs Also See for KSV26HRC:

Advertisement

H6, Indoor unit. (Indoor Fan Stall)
Indoor Standby LED, flashing 11 times.
Yellow LED, Outdoor unit flashing 6 times. (High Temp Prevention)
Red LED, Outdoor unit flashing 3 times. (High Temp Prevention)
# Check if the filters are blocked on the indoor unit.
# Check the refrigerant charge.
# Check for blockages within the refrigerant system.
# Check the evaporator fan motor for correct operation. If the fan motor is not operating check the five
pin DC-Motor connector plug on the indoor PCB for correct termination.
# Check for DC voltage between the Black & Yellow wires located at the DC-Motor connector plug:
Cooling Mode
1 speed: 3.02 Volts DC.
2 speed: 3.18 Volts DC.
3 speed: 3.37 Volts DC.
4 speed: 3.54 Volts DC.
5 speed: 3.68 Volts DC.
Turbo speed: 4.32 Volts DC.
Note: If the above DC voltage readings are available, yet the indoor fan motor is not operational, replace
the indoor fan motor.
Note: If the DC volts are not available at the above set points, replace the indoor PCB.
Page 24 KSSSI113
Black & Yellow wires on five pin indoor DC-Motor connector plug.
Heating Mode
1 speed: 3.33 Volts DC.
2 speed: 3.45 Volts DC.
3 speed: 3.56 Volts DC.
4 speed: 3.66 Volts DC.
5 speed: 4.00 Volts DC.
Turbo speed: 4.25 Volts DC.

Hide quick links:

Advertisement

loading

This manual is also suitable for:

Ksv35hrc