EUCHNER CES-A-C5H-EX Operating Instructions Manual

Unicode/multicode non-contact safety switch
Hide thumbs Also See for CES-A-C5H-EX:

Advertisement

Quick Links

Operating Instructions
Non-Contact Safety Switch
EN
CES-A-C5H-EX Unicode/Multicode

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the CES-A-C5H-EX and is the answer not in the manual?

Questions and answers

Summary of Contents for EUCHNER CES-A-C5H-EX

  • Page 1 Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX Unicode/Multicode...
  • Page 2: Table Of Contents

    10.1. Notes about .........................15 10.2. Safety in case of faults ........................15 10.3. Requirements for connection cables ....................15 10.4. Connector assignment of safety switch CES-A-C5H-EX ..............16 10.5. Correct connection ........................17 10.6. Connection example ........................18 Setup ......................... 19 11.1. LED displays ..........................19 11.2.
  • Page 3 Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX Technical data ....................22 13.1. Safety switch CES-A-C5H-EX ......................22 13.1.1. Technical data for safety switch CES-A-C5H-EX ..............23 13.1.2. Typical system times ......................24 13.2. Actuator CES-A-BPA-EX ........................25 13.2.1. Technical data .........................25 13.2.2. Typical operating distance ....................26 13.2.3.
  • Page 4: About This Document

    Non-Contact Safety Switch CES-A-C5H-EX 1. About this document 1.1. Scope These operating instructions are valid for all CES-A-C5H-EX. These operating instructions, the document “Safety information and maintenance” and any enclosed data sheet form the complete user information for your device. 1.2. Target group Design engineers and installation planners for safety devices on machines, as well as setup and servicing staff possessing special expertise in handling safety components.
  • Page 5: Correct Use

    Ì EN 60079-14 Ì EN 60079-31 The safety switch must be used only in conjunction with the designated CES actuators from EUCHNER. On the use of different actuators, EUCHNER provides no warranty for safe function. Important! Ì Devices with ATEX rating may be operated only with actuators that also have an ATEX rating for the same zone.
  • Page 6: Description Of The Safety Function

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX Table 1: Possible combinations for CES components Actuator Safety switch CES-A-BBA-EX CES-A-BPA-EX 098158 102125 CES-A-C5H-EX Combination possible Combination possible, guard locking for process protection Key to symbols Combination possible, guard locking for personnel protection...
  • Page 7: Explosion Protection Safety Concept

    … Dc X = To prevent electrostatic charging, do not subject the switch to any processes that generates a large amount of charge. Safety switches with ATEX identification marking from EUCHNER are not safety devices as defined by the ATEX Directive. The specified type of protection ic applies only to the integrated reader module. The electrical circuits in the device connec- tion (M12 plug connector) are not intrinsically safe! If mounted on heat/cooling sources, the permissible ambient temperature (see technical data) must be observed.
  • Page 8: General Safety Precautions

    Prior to use, read the operating instructions and keep these in a safe place. Ensure the operating instructions are always available during mounting, setup and servicing. EUCHNER cannot provide any warranty in relation to the readability of the CD for the storage period required. For this reason you should archive a printed copy of the operating instructions.
  • Page 9: Function

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 7. Function The safety switch monitors the position of movable guards. The safety outputs are switched on/off when the actuator is moved to/removed from the operating distance. The system consists of the following components: coded actuator (transponder) and switch.
  • Page 10: Block Diagram

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 7.3. Block diagram Coded Trans- actuator ponder Output circuit: Power supply Read head with for load A Read head evaluation unit Load A CES-A-.5 -LAB Common ground for output A and B Pin assignment:...
  • Page 11: Changing The Approach Direction

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 8. Changing the approach direction NOTICE Risk of damage to equipment as a result of trapped cables. Ì Make sure that the cables are not trapped or torn off when the approach direction is changed.
  • Page 12: Mounting

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 9. Mounting WARNING On use in potentially explosive atmospheres the following applies: Ì Protection against mechanical effects on the switch: - Install switch so that the rear of the housing is entirely covered in order to protect it from me- chanical damage through impact.
  • Page 13: Operating Instructions

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX Note the following points: Ì Actuator and safety switch must be easily accessible for inspection and replacement. Ì Actuator and safety switch must be fitted so that - the front faces are at the minimum switch-on distance 0.8 x S or closer when the guard is closed.
  • Page 14: Electrical Connection

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 10. Electrical connection WARNING Loss of the safety function due to incorrect connection. Ì Not suitable for safety relays that realize short-circuit monitoring with different potentials (0 V/24 V). The voltage at +LA/+LB must correspond to the information in the technical data.
  • Page 15: Notes About

    Danger of explosion or malfunctions as a result of incorrect connection cables. Ì For connecting cables, the requirements in the following table apply. EUCHNER provides no war- ranty for safe function in case of failure to comply with these requirements.
  • Page 16: Connector Assignment Of Safety Switch Ces-A-C5H-Ex

    (safety relay) 51 - 100 101 - 300 1 - 15 16 - 50 (e.g. small contactor) 51 - 100 101 - 300 10.4. Connector assignment of safety switch CES-A-C5H-EX   + UB   -LAB   ...
  • Page 17: Correct Connection

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 10.5. Correct connection WARNING If there is a mistake, loss of the safety function due to incorrect connection. Ì To ensure safety, both safety outputs (LA and LB) must always be evaluated. Ì To achieve category 3/4 according to EN ISO 13849-1, it is necessary to monitor the downstream contactors.
  • Page 18: Connection Example

    The user is responsible for safe inte- gration into the overall system. Detailed application examples can be found at www.euchner.com. Simply enter the order number in the search box. All available connection examples for the device can be found in “Downloads.”...
  • Page 19: Setup

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 11. Setup 11.1. LED displays Color State Meaning illumi- Normal operation nated STATE green - Teach-in operation flashing (for further signal function, see chapter 12. System status table on page 21) illumi- yellow Valid actuator detected...
  • Page 20: Carrying Out Teach-In For A New Actuator

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 11.2.2. Carrying out teach-in for a new actuator A maximum of eight teach-in operations can be undertaken. The number of already completed teach-in operations is signaled by the flashing sequence of the STATE LED each time the power supply is connected (see 12. System status table on page 21, area Status indication).
  • Page 21: System Status Table

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 12. System status table LED indicator Output Output Operating mode State closed Normal operation, door closed Normal operation open Normal operation, door open open 4 Hz Initial setup after delivery, ready for first teach-in operation...
  • Page 22: Technical Data

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 13. Technical data NOTICE If a data sheet is included with the product, the information on the data sheet applies. Approvals 13.1. Safety switch CES-A-C5H-EX Ì Read head and evaluation unit integrated in the normal housing Ì...
  • Page 23: Technical Data For Safety Switch Ces-A-C5H-Ex

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 13.1.1. Technical data for safety switch CES-A-C5H-EX Value Parameter Unit min. typ. max. Housing material PBT GF30 Dimensions According to EN 60947-5-2 Weight Ambient temperature at U = DC 24 V °C Degree of protection IP65/IP 67...
  • Page 24: Typical System Times

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 13.1.2. Typical system times Please refer to the technical data for the exact values. Ready delay: After switching on, the device carries out a self-test. The system is ready for operation only after this time.
  • Page 25: Actuator Ces-A-Bpa-Ex

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 13.2. Actuator CES-A-BPA-EX Ì Cube-shaped design 40 x 40 mm ATEX rating II 3G Ex ic IIC T6 Gc II 3D Ex ic IIIC T85°C Dc X Dimension drawing for CES-A-BPA-EX - 0,25 CES-A-BPA-EX IP67 Active face...
  • Page 26: Typical Operating Distance

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 13.2.2. Typical operating distance Only in conjunction with actuator CES-A-BPA-EX on surface mounting. - 4 5 - 4 5 For a side approach direction for the actuator and read head, a minimum distance of s = 6 mm must be maintained so that the operating distance of the side lobes is not entered.
  • Page 27: Actuator Ces-A-Bba-Ex

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 13.3. Actuator CES-A-BBA-EX Ì Cube-shaped design 42 x 25 mm ATEX rating II 3G Ex ic IIC T6 Gc II 3D Ex ic IIIC T85°C Dc X Approvals Dimension drawing for CES-A-BBA-EX CES-A-B BA-EX 32 ±0,1 Active face Active face 2 safety screws M4 X 14...
  • Page 28: Typical Operating Distance

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 13.3.2. Typical operating distance Only in combination with actuator CES-A-BBA-EX. - 3 0 - 3 0 For a side approach direction for the actuator and safety switch, a minimum distance of s = 4 mm must be maintained so that the operating distance of the side lobes is not entered.
  • Page 29: Ordering Information And Accessories

    14. Ordering information and accessories Tip! Suitable accessories, e.g. cables or assembly material, can be found at www.euchner.com. To order, enter the order number of your item in the search box and open the item view. Accessories that can be combined with the item are listed in “Accessories.”...
  • Page 30: Declaration Of Conformity

    Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 17. Declaration of conformity (Translation of the original operating instructions) 2110182-09-12/18...
  • Page 31 Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX 2110182-09-12/18 (Translation of the original operating instructions)
  • Page 32 Edition: 2110182-09-12/18 Title: Operating Instructions Non-Contact Safety Switch CES-A-C5H-EX (Translation of the original operating instructions) Copyright: © EUCHNER GmbH + Co. KG, 12/2018 Subject to technical modifications; no responsibility is accept- ed for the accuracy of this information.

This manual is also suitable for:

Ces-a-.5

Table of Contents