Siemens FCI2016-U1 Mounting & Installation page 6

Periphery board (250p) / periphery board (500p)
Table of Contents

Advertisement

Periphery board (250p) FCI2016
1
Description
6 | 46
Building Technologies
Siemens Industry, Inc.
Properties
Two different power supplies can be connected:
Power supply (170 W) FP2011 only for fire control panels with a maximum load
of 6.5 A
Power supply (300 W) FP2012 for fire control panels and voice alarm fire
control panels with a maximum loading of 11.5 A
Power supply (300 W) FP2012 for voice alarm fire control panels in housings
(3HU) with a maximum loading of 22 A
Battery charger capable of charging up to 100 Ah batteries at a maximum of 6 A.
Power supply (300W) FP2012 must be used for batteries of more than 33 Ah.
Power supply (170W) FP2011 must be used for batteries of 33 Ah or less
Ground faults detected at <1 kΩ to ground
Ground fault detection for all circuits except the 2 detector circuits handled by PMI.
Each detector core has its own ground fault and supervision circuit.
One integrated FDnet/C-NET circuit card for circuits 1 and 2 and EMC surge
protection for four style 4 or two style 6 circuits.
Maximum of 252 device addresses can be controlled per integrated FDnet/C-NET
circuit card.
Three relay outputs and one user programmable relay output for common alarm,
common trouble, common supervision, and user programmable.
The auxiliary output is a regulated DC 24 V output with a maximum of 1.5 A.
Degraded alarm and trouble mode functions when either or both CPUs for the
periphery board or PMI are compromised.
Integrated NAC circuit, specified for DC 24 V, configured for either one class A
(style Z) or two class B (style Y) circuits, with a maximum of 3 A for one class A or
max. 3 A for each of the two class B circuits. NACs have integrated
synchronization protocol for audible or visual notification appliances.
All NAC circuits are supervised and protected for overcurrent and direct short-
circuited output.
Two slots for optional extensions, one of which is for NAC module (1A/2B) or
releasing module (XCI2001):
NAC module (1A/2B) FCI2001 for one additional class A circuit or two class B
circuits (same data as integrated NAC circuit) (P/N S54400-A54-A1). The
module connects to X901.
Releasing module (XCI2001) (P/N S54400-A69-A1) The module connects to
X901.
Leased line or city tie module FCI2020 (P/N 54400-A57-A1). The module
connects to X902.
Additional peripheral data bus connection (X202) for LED or DACT modules.
Main CPU and detector core CPUs capable of being updated in the field through
the PMI.
A6V10315038_f_en_--
2016-02-25

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fci2017-u1

Table of Contents