Periphery board (250p) FCI2016
1
Technical data
Bell follower input
Detector circuits
Relay contacts
22 | 46
Building Technologies
Siemens Industry, Inc.
Plug strip
Voltage
Curent
Design
Terminal strips
Output voltage
Number of integrated circuit
cards
Output current per integrated
circuit card
Addressable devices per
integrated circuit card
Connectable circuits per
integrated circuit card
Protocol
Circuit resistance
Capacity
Cable types
Connectable devices
Monitored for
Design
Plug strip
Design
Switching voltage
Switching current
X1001
DC 24 V filtered or full wave
Max. 4 mA
Voltage surge protection
X1401 circuit card 1, circuit 1
X1402 circuit card 1, circuit 2
DC 24 V, filtered
1
Max. 500 mA
Max. 252
2 style 6 or 4 style 4 (mixed variants are possible)
FDnet/C-NET
Max. 180 Ω
500 nF per circuit
All (twisted recommended)
You will find detailed specifications in the following
documents:
●
A6V10315013 for Desigo
●
A6V10333396 for Cerberus PRO
See 'List of compatibility'
●
Ground fault
●
Short circuit
●
Open circuit
●
Circuit capacitance
●
Short-circuit-proof
●
Voltage surge protection
●
Open circuit
●
Power limited
X1201
●
Relay output
●
Break or make contact
●
Nonpower limited
●
Alarm and trouble active in degraded mode
operation
DC 30 V or AC 120/240 V ohmic
5 A @ DC 30 V or AC 120 V
4 A @ AC 240 V
A6V10315038_f_en_--
2016-02-25