Siemens FCI2016-U1 Mounting & Installation page 43

Periphery board (250p) / periphery board (500p)
Table of Contents

Advertisement

Bell follower input
Detector circuits
Relay contacts
Building Technologies
Siemens Industry, Inc.
Plug strip
Voltage
Curent
Design
Terminal strips
Output voltage
Number of integrated circuit cards
Output current per integrated circuit card
Addressable devices per integrated circuit
card
Connectable circuits per integrated circuit
card
Protocol
Circuit resistance
Capacity
Cable types
Connectable devices
Monitored for
Design
Plug strip
Design
Switching voltage
Switching current
Periphery board (500p) FCI2017
Technical data
X1001
DC 24 V filtered or full wave
Max. 4 mA
Voltage surge protection
X1401 circuit card 1, circuit 1
X1402 circuit card 1, circuit 2
X1801 circuit card 2, circuit 3
X1802 circuit card 2, circuit 4
DC 24 V, filtered
2
Max. 500 mA
Max. 252
2 style 6 or 4 style 4 (mixed variants are
possible)
FDnet/C-NET
Max. 180 Ω
500 nF per circuit
All (twisted recommended)
You will find detailed specifications in the
following documents:
A6V10315013 for Desigo
A6V10333396 for Cerberus PRO
See List of compatibility
Ground fault
Short circuit
Open circuit
Circuit capacitance
Short-circuit-proof
Voltage surge protection
Open circuit
Power limited
X1201
Relay output
Break or make contact
Nonpower limited
Alarm and trouble active in degraded
mode operation
DC 30 V or AC 120/240 V ohmic
5 A @ DC 30 V or AC 120 V
4 A @ AC 240 V
A6V10315038_f_en_--
2
43 | 46
2016-02-25