Electrical Data and Specifications
Electrical Requirements
Use ONLY wire size recommended for
Wire Size
single outlet branch circuit.
Fuse/Circuit
Use ONLY type and size fuse or HACR cir-
Breaker
cuit breaker indicated on unit's rating guide.
Proper over current protection to the units is
the responsibility of the owner.
Grounding
Unit MUST be grounded from branch circuit
to unit, or through separate ground wire
provided on permanently connected units.
Ensure that branch circuit or general pur-
pose outlet is grounded.
Wire Sizing
Use recommended wire size given in tables
and install a single branch circuit. All wiring
must comply with local and national codes.
NOTE: Use copper conductors only.
WARNING
Electrical Shock Hazard.
Turn OFF electric power before service or instal-
lation.
Unit must be properly grounded.
Unit must have correct fuse or circuit breaker pro-
tection. Unit's supply circuit must have the correct
wire conductor size. All electrical connections and
wiring must be installed by a qualified electrician
and conform to the National Electrical Code and all
local codes which have jurisdiction. Failure to do so
can result in property
damage, personal injury and/or death.
NOTE: All 230/208 chassis must be hard wired with a properly sized breaker. See unit nameplate for specific electrical requirements.
Use HACR type breakers to avoid nuisance trips. All field wiring must be done in accordance with NEC and local codes. It is the in-
staller's responsibility to ensure that the electrical codes are met.
Electrical Rating Table
NOTE: Use copper conductors ONLY. Wire sizes are per NEC.
Recommended Branch Circuit Sizes*
Nameplate Maximum Circuit Breaker Size
15A
20A
30A
AWG - American Wire Gauge
* Single circuit from main box.
** Based on 100' or less of copper, single insulated conductor at 60˚ C
AWG Wiring Size**
14
12
10
7