Description
Designed for the purpose of raising an alarm
manually
once
verification
emergency condition exists, by pressing the
non breakable glass. Meets the standard
requirement of EN 54 part 11, European
Standard and approved by Loss Prevention
Certificate Board (LCPB).
The I-9202 constructed of high impact red
ABS with a modern pleasing appearance.
The terminating back box enables first fix
installation and termination leaving the fascia
with integral electronics to be simply plugged
into base at the time of commissioning. Non
breakable glass that can be reset with the
GST standard reset key.
The I-9202 operated via a micro-switch that
when pressed a signal will be transmitted
and the volt free contact will be latched.
Contain integral LED indicator to denote
operational mode.
Electronic addressing can be done through
Handheld Programming device (P-9910B),
purchased separately.
I-9202
Technical Specifications
Mounting Base
The location of manual call point should be
installed in compliance with all local codes
and / or NFPA 72 National Fire Alarm Code,
NFPA 70 National Electrical Code.
Installed
electrical box.
of
a
fire
or
 Standard: EN54-part 11
 Protection rating: IP 40
 Operating voltage: 24Vdc Loop
 Operating current:
Standby current 0.8mA
Alarm Current 2mA
 Operating temperature: -10°C to
+50°C
 N/O Output contact: 60Vdc, 0.1A
 Contact resistance: 100mΩ
 Relative humidity: 95%
 Application: Indoor use
 Visual Indicator: LED, Red ( lit
steady when alarm, 3 sec interval
blinking at normal state)
 Material and colour: ABS, red
 Wiring: 1 pair non polarized
 Dimensions: 97x100x45.5mm
onto
a
standard
     
   
   
     
       
       
   
one
gang
  
          
       

Advertisement

loading
Need help?

Need help?

Do you have a question about the I-9202 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for GST I-9202

  • Page 1 Meets the standard requirement of EN 54 part 11, European Standard and approved by Loss Prevention Certificate Board (LCPB). The I-9202 constructed of high impact red       ABS with a modern pleasing appearance.   ...
  • Page 2 Connect the wires to the required terminal Compatible with all GST Fire Alarms Panels according to the wire diagram. The Z1, Z2 is GST 100, GST 200, GST 500, GST 5000, for addressable Loop, non-polarized while the GST 9000. K1, K2 is intended to normally open passive contacts, can provide 100mA/24Vdc capacity..