ABB LevelMaster 7100 Application Manual page 13

Liquid level sensor, upgrade kit, upgrade to support batteryless floats
Hide thumbs Also See for LevelMaster 7100:
Table of Contents

Advertisement

To configure the new board:
1.
Connect the laptop directly to the electronic board using the correct cable and
adapters for the board.
2.
Start the MasterLink version 2.0 software.
3.
Click the Comm. Port drop down list.
4.
Select the laptop communication port used.
1.
Leave Baud Rate at 9600 (factory default).
2.
Click Setup LevelMaster.
3.
Select I have only one LevelMaster connected to communication port and I
want to set it up.
4.
Click Setup LevelMaster.
5.
Observe the messages displayed on the monitor screen. Verify that the
communication is successful. The screen should indicate the number of tries
and 100% success.
6.
When prompted to add the LevelMaster to the list, click No. The unit can be
added later.
7.
If using the existing configuration, proceed to section 4.5.2, Configure the new
electronic board with the existing configuration.
8.
If using a default configuration file, proceed to section 4.5.3, Configure the new
electronic board with a default configuration.
4.5.2 Configure the new electronic board with the existing configuration
Use this procedure if configuring the new board with the existing configuration file
saved in section 4.3.3, Save the configuration.
In this procedure the existing configuration is downloaded to the new board. The ID,
baud rate, and calibration data from the previous board are saved in the unit. The
float configuration must be changed to reflect the batteryless floats.
To download the existing configuration:
1.
Select the Upload/Download tab.
2.
Under Send data to the LevelMaster from the file, click the browse ([...]) button.
3.
At the browser, navigate to the folder where the existing configuration file was
saved (for example, C:\Program Files (x86)\ABB\MasterLink).
4.
Locate and select the configuration file.
5.
Click Open.
6.
Click Download Data to LevelMaster.
7.
Click OK when download is complete.
8.
Click the Setup tab.
9.
Under Make Hardware change, click Hardware change.
10. In the Select category drop down list, select Float Configuration.
11. Click Next.
12. Select Float mode Dual Batteryless.
13. Click Next.
14. Click Next again to confirm that the float configuration will be changed.
15. Click OK when configuration change is complete.
2105824-001 rev. AA | 13