4.
Plug the 16-pin connector from the sensor assembly into the new electronic
board. The connector is keyed so it will only plug in one way. Push some of the
excess cable back down through the bottom of the sensor assembly while
sliding the electronic board back into position. Allow a small cable loop to fold
back towards the top of the enclosure.
5.
Brace the electronic board inside the housing by using the yellow fiberglass tab
inserted into the enclosure.
6.
Bend the tab gently into a semicircle using the thumb and forefinger, making
sure the apex of the arch is placed against the board while the ends of the tab
are braced to the inside of the housing.
7.
Proceed to configure the board.
4.5
Configure the new board
MasterLink version 2.0 is required to configure the new board.
4.5.1 Connect to the new board
To connect use the following (see Table 2 in section 3.4, Required tools and
materials, in page 6, for details):
— The RS485 to RS232 converter (2100241 – 005) with the cable adapter
(2100250 – 002, the cable with two separate terminal connectors at one end)
— If using an USB port on the laptop, use the serial-to-USB adapter.
IMPORTANT NOTE: Make sure to connect the positive terminal (red
wire) to the positive contact on the battery holder.
12 | 2105824-001 rev. AA
RS485
PORT
REMOVE
TERMINAL
CONNECTORS
Figure 5: Removing terminal connectors
POWER
PORT