Reliable DDX PrePaK D Instructions For Installation, Operation Care And Maintenance

Reliable DDX PrePaK D Instructions For Installation, Operation Care And Maintenance

Preaction system 4"/6"/8" 100mm/150mm/200mm, 10 psi 0.7 bar pneumatic supervising pressure, single/double interlock - electric/electric release

Advertisement

Quick Links

Instructions for
Installation, Operation,
Care and Maintenance
10 PSI (0.7 bar) Pneumatic Supervising Pressure
Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523
Model DDX PrePaK, Type D
Preaction System
4"(100mm), 6" (150mm) &
8" (200mm)
Single Interlock - Electric Release
Double Interlock - Electric/Electric Release
Contents
Listings and Approvals
Inspection, Testing and Maintenance
Diagrams:
Assembly Dimensions
Terminal Box Wiring
Factory Installed Electrical Devices
Detector Circuit Wiring
Output Device Wiring
Component Identification/System Setup
Potter Panel Programming
Bulletin 733
F
Rev.
Page
2
4
4
5
5-6
6
6-7
3
8
9
10-11
12-13
14
15-16
17-26
27-28

Advertisement

loading
Need help?

Need help?

Do you have a question about the DDX PrePaK D and is the answer not in the manual?

Questions and answers

Summary of Contents for Reliable DDX PrePaK D

  • Page 1: Table Of Contents

    Potter PFC-4410-RC Releasing Control Panel Terminal Box Wiring Factory Installed Electrical Devices 10-11 Detector Circuit Wiring 12-13 Output Device Wiring Component Identification/System Setup 15-16 Potter Panel Programming 17-26 Ordering Information 27-28 Reliable Automatic Sprinkler Co., Inc., 103 Fairview Park Drive, Elmsford, New York 10523...
  • Page 2: General Description

    General Description solenoid valve, when closed, preserves supply water pressure The Reliable Model DDX 4” (100 mm), 6” (150mm) & 8” in the Model DDX valve’ s push-rod chamber. Actuating the sole- (200mm) PrePaKs are completely self-contained, supervised noid valve releases that water pressure which allows the Model preaction systems that can be readily installed within a floor DDX valve to open.
  • Page 3 Fig. 1...
  • Page 4: Technical Data

    (120mm) (19mm) (150mm) ” (19mm) 1. The Reliable Model DDX 4” (100 mm), 6” (150 mm) and 8” Class (200mm) PrePaKs are rated for a minimum supply pres- sure of 20 psi (1.4 bar) and a maximum supply pressure of The following is a list of Technical Data Bulletins which de- 250 psi (17.2 bar).
  • Page 5: Installation Requirements

    Reliable Model DDX 4” (100 mm), 6” (150 mm) 3. A normally-closed, releasing solenoid valve, which is used and 8” (200 mm) PrePaKs must be UL and/or ULC Listed or FM to actuate the deluge valve.
  • Page 6: System Operation

    This causes valve F, into the drip cup or drain manifold, G. If no leak the clapper to open. Refer to Reliable Bulletins 518 and 519 for occurs, the deluge valve’ s clapper is sealed. Open slowly, further details.
  • Page 7 Inspection And Testing Of Single And Double 4. Step #3 should result in a sudden drop of water pressure Interlock Systems in the deluge valve’ s push-rod chamber via an energized Refer to Fig. 9 or 10. solenoid valve. 1. Water supply — Verify that the valve controlling wa- 5.
  • Page 8: System Reset Procedure

    RED OUTPUT LED STEADY: ABORT ZONE 1 OUTPUT 1 ZONE 2 OUTPUT 2 ZONE 3 OUTPUT 3 PROGRAM ZONE 4 OUTPUT 4 MODE MODE AC POWER SUP 1/ABORT SCROLL-UP BUZZER SILENCE POWER TBL SUPERVISORY 2 SYSTEM TBL COMMON ALARM LAMP SUP TBL ALARM SILENCE TEST...
  • Page 9 Fig. 3...
  • Page 10 Fig. 4...
  • Page 11 Fig. 5...
  • Page 12 Fig. 6...
  • Page 13 Fig. 7...
  • Page 14 Fig. 8 — Wiring Diagram...
  • Page 15 Fig. 9...
  • Page 16 Fig. 10...
  • Page 17 Potter Program #6 Single Interlock Programming Instructions (Single Hazard; 2 Alarm Zones, 1 Waterfl ow Zone, and 2 Supervisory Zones) 1. Apply power to panel. 2. Slide the program switch down. 3. Press the FUNCTION button until the display reads “PASS- WORD=000.”...
  • Page 18 Fig. 11 — Wiring Diagram...
  • Page 19 Potter Program #7 Single Interlock Programming Instructions (Single Hazard - Cross-Zoned, 2 Alarm Zones, 1 Waterfl ow Zone and 2 Supervisory Zones) 1. Apply power to panel. 5. Press the FUNCTION button until the display reads “PRO- 2. Slide the program switch down. GRAM ##.”...
  • Page 20 Fig. 12...
  • Page 21 Potter Program #9 Double Interlock Programming Instructions (Single Hazard, Cross Zoned, 2 Alarm Zones (1 Detection & 1 Low Air), 1 Waterfl ow Zone, and 1 Supervisory Zone) 5. Press the FUNCTION button until the display reads “PRO- 1. Apply power to the panel. GRAM ##.”...
  • Page 22 Fig. 13...
  • Page 23 Potter Program #10 Double Interlock Programming Instructions (Single Hazard, Cross Zoned, 3 Alarm Zones (2 Detection & 1 Low Air), 1 Waterfl ow Zone, and 1 Supervisory Zone) 5. Press the FUNCTION button until the display reads “PRO- 1. Apply power to the panel. GRAM ##.”...
  • Page 24 Fig. 14...
  • Page 25 Custom Program #1 11. Press the SELECT button until the display reads “PRO- (For New York City Compliance) GRAM #0.” Single Interlock Programming Instructions for 12. Press the SET button. New York City Compliance (Single Hazard, 2 Alarm 13. Press the FUNCTION button until the display reads “OUT- Zones, 1 Waterfl...
  • Page 26 Fig. 15...
  • Page 27: Potter Pfc-4410-Rc Releasing Control Panel

    Ordering Information: Model DDX 4” (100mm) & 6” (150mm) PrePAK Part Number Code Key 4 = PrePaK Assembly 175 = 175 psi 0 = No with 4” (100 mm) (12.1 bar) Releasing/Control Panel Grooved Ends System Pressure Model Rating 1 = Potter 0 = No Air Compressor DDX Deluge Valve PFC-4410-RC...
  • Page 28 Fig. 16...