Page 1
Model DDX PrePaK, Type D Preaction System 4”(100mm) & 6”(150mm) Instructions for Single Interlock Installation Operation Double Interlock Care and Maintenance 10 psi (0,7 bar) Pneumatic Supervising Pressure The Reliable Automatic Sprinkler Co., Inc. 103 Fairview Park Drive , Elmsford, New York 10523...
In the event that the system piping is ruptured or a The Model DDX PrePaK can be used in both single and sprinkler head is accidentally opened, the system pressure double interlock applications. Reliable Single and Double switch will operate and an alarm will sound.
Zone and 2 Supervisory Zones Technical Data 1. The Reliable Model DDX 4” (100 mm) and 6” (150 mm) Refer to Potter Manual # 5403550 included with the PrePak, for other PrePaKs are rated for a minimum supply pressure of 20 programming options available.
Page 5
System Operation (Single Interlock) bar), if necessary, is accomplished by first loosening the To fully activate (water flow) the Reliable Model DDX 4” locknut on the air pressure regulator and turning the (100 mm) or 6” (150 mm) PrePaK in a single interlock adjustment screw (refer to Fig.
System Operation (Double Interlock) Resetting Single And Double Interlock Systems To fully activate (water flow) the Reliable Model DDX 4” (100 mm) or 6” (150 mm) PrePaK in a double interlock Refer to Fig. 8. application, two independent events must coexist. An 1.
Page 13
Inspection And Testing Of Single And Testing The Model DDX PrePaK Without Double Interlock Systems Causing Water Flow Refer to Fig. 8. Refer to Fig. 8. 1. Water supply — Verify that the valve controlling water 1. Close the main valve controlling water supply to the supply to the deluge valve is opened fully and properly deluge valve and open drain valve B.
Page 15
Potter Program #6 Single Interlock Programming Instructions (Single Hazard; 2 Alarm Zones, 1 Waterflow Zone, and 2 Supervisory Zones) 1. Apply power to panel. 5. Press the FUNCTION button until the display reads 2. Slide the program switch down. “PROGRAM ##.” (the second "#" character refers to the 3.
Page 17
Potter Program #7 Single Interlock Programming Instructions (Single Hazard - Cross-Zoned, 2 Alarm Zones, 1 Waterflow Zone and 2 Supervisory Zones) 5. Press the FUNCTION button until the display reads 1. Apply power to panel. “PROGRAM ##.” (the second "#" character refers to the 2.
Page 19
Potter Program #9 Double Interlock Programming Instructions(Single Hazard, Cross Zoned, 2 Alarm Zones(1 Detection & 1 Low Air), 1 Waterflow Zone, and 1 Supervisory Zone) 5. Press the FUNCTION button until the display reads 1. Apply power to the panel. "PROGRAM ##."...
Page 21
Potter Program #10 Double Interlock Programming Instructions (Single Hazard, Cross Zoned, 3 Alarm Zones (2 Detection & 1 Low Air), 1 Waterflow Zone, and 1 Supervisory Zone) 5. Press the FUNCTION button until the display reads 1. Apply power to the panel. “PROGRAM ##.”...
Page 23
Custom Program #1 (For New York City Compliance) Single Interlock Programming Instructions for New York City Compliance (Single Hazard, 2 Alarm Zones, 1 Waterflow Zone, and 2 Supervisory Zones) 12. Press the SET button. 1. Apply power to the panel. 13.
Example: 4 - 175 - 1 - 1 - 1 4" (100 mm) Model DDX PrePaK Assembly with 175 psi (12,1 bar) System Pressure Rating, cULus / FM Approved Pressure Switches, ¾ Hp Air Compressor Factory Wired to 120 VAC @ 60 Hz, and Potter PFC-4410-RC...
Page 26
Mutual Research Corporation, or other similar organizations and also with the provisions of governmental codes or ordinances whenever applicable. Products manufactured and distributed by Reliable have been protecting life and property for over 80 years, and are installed and serviced by the most highly qualified and reputable sprinkler contractors located throughout the United States, Canada and foreign countries.