Shutter actuator 4gang 6A 230V manual
RMD
75314013
Application:
Depending on EIB telegrams received, the shutter actuator switches up to four independent output
channels, one for each motor (4-channel operation). The number of output channels can also be reduced
to two so that up to two blind/shutter motors can be controlled per channel (2 x 2-channel operation).
The shutter actuator is equipped with a manual control feature permitting bus-independent operation of
the individual outputs in a permanent or temporary mode.
On reception of a storm warning, the actuator can, for instance, move the shutter into a predefined safety
position and lock them there. Each output can be independently parameterized for individual moving
times.
Illustration:
N
L
L
L
L
A1
OFF
Dimensions:
Width:
4 modules, 72 mm
Height:
90 mm
Depth:
64 mm
Degree of protection:
Mark of approval:
Ambient temperature:
Storage temperature:
Fitting position:
Minimum distances:
Type of fixing:
instabus EIB supply
Voltage:
Power consumption:
Connection:
External supply
Voltage:
Total power dissipation:
Connection:
© Gebr. Berker 2005
(Subject to prior change)
A 2
A1
L
A 4
L
A3
A2
A3
A4
IP 20
KNX / EIB
-5 ° C ... +45 ° C
-25 ° C ... +70 ° C (reduced lifetime when stored abo ve +45° C)
any
none
snap-fastening on DIN rail (no data rail required)
21 – 32 V DC (SELV)
max. 150 mW
instabus connecting and branching terminal
110 V (-10 %) - 240 V (+10 %) AC; 50 / 60 Hz (no DC)
min. 0.3 W up to max. 1.8 W (no load connected)
screw terminals:
Documentation
Controls:
1 programming button
1 programming LED (red)
Manual controls:
1 "
" key for manual control mode
activation (select key)
1 "OFF" key (ALL stop)
1 "
" key for manual UP movement
1 "
" key for manual DOWN movement
Status indicators:
8 LEDs (red) to indicate the movement
direction of the individual outputs or of the
manually selected output
1 LED (red) to indicate the "permanent
manual mode"
1 LED (red) to indicate the "UP" movement of
the manually selected output
1 LED (red) to indicate the "DOWN"
movement of the manually selected output
(For further information on controls and status
indicators cf. "Manual control")
0.5 – 4
mm² single wire and stranded without ferrule
0.5 – 2.5
mm² stranded wire with ferrule
Version: 10.05.2005
75314013.doc
Technical
Page: 1 / 17