Berker RMD 75314013 Technical Documentation Manual
Berker RMD 75314013 Technical Documentation Manual

Berker RMD 75314013 Technical Documentation Manual

Shutter actuator 4gang 6a 230v

Advertisement

Quick Links

Shutter actuator 4gang 6A 230V manual
RMD
75314013
Application:
Depending on EIB telegrams received, the shutter actuator switches up to four independent output
channels, one for each motor (4-channel operation). The number of output channels can also be reduced
to two so that up to two blind/shutter motors can be controlled per channel (2 x 2-channel operation).
The shutter actuator is equipped with a manual control feature permitting bus-independent operation of
the individual outputs in a permanent or temporary mode.
On reception of a storm warning, the actuator can, for instance, move the shutter into a predefined safety
position and lock them there. Each output can be independently parameterized for individual moving
times.
Illustration:
N
L
L
L
L
A1
OFF
Dimensions:
Width:
4 modules, 72 mm
Height:
90 mm
Depth:
64 mm
Degree of protection:
Mark of approval:
Ambient temperature:
Storage temperature:
Fitting position:
Minimum distances:
Type of fixing:
instabus EIB supply
Voltage:
Power consumption:
Connection:
External supply
Voltage:
Total power dissipation:
Connection:
© Gebr. Berker 2005
(Subject to prior change)
A 2
A1
L
A 4
L
A3
A2
A3
A4
IP 20
KNX / EIB
-5 ° C ... +45 ° C
-25 ° C ... +70 ° C (reduced lifetime when stored abo ve +45° C)
any
none
snap-fastening on DIN rail (no data rail required)
21 – 32 V DC (SELV)
max. 150 mW
instabus connecting and branching terminal
110 V (-10 %) - 240 V (+10 %) AC; 50 / 60 Hz (no DC)
min. 0.3 W up to max. 1.8 W (no load connected)
screw terminals:
Documentation
Controls:
1 programming button
1 programming LED (red)
Manual controls:
1 "
" key for manual control mode
activation (select key)
1 "OFF" key (ALL stop)
1 "
" key for manual UP movement
1 "
" key for manual DOWN movement
Status indicators:
8 LEDs (red) to indicate the movement
direction of the individual outputs or of the
manually selected output
1 LED (red) to indicate the "permanent
manual mode"
1 LED (red) to indicate the "UP" movement of
the manually selected output
1 LED (red) to indicate the "DOWN"
movement of the manually selected output
(For further information on controls and status
indicators cf. "Manual control")
0.5 – 4
mm² single wire and stranded without ferrule
0.5 – 2.5
mm² stranded wire with ferrule
Version: 10.05.2005
75314013.doc
Technical
Page: 1 / 17
Part 7

Advertisement

loading
Need help?

Need help?

Do you have a question about the RMD 75314013 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Berker RMD 75314013

  • Page 1 Total power dissipation: screw terminals: Connection: 0.5 – 4 mm² single wire and stranded without ferrule 0.5 – 2.5 mm² stranded wire with ferrule © Gebr. Berker 2005 Version: 10.05.2005 Page: 1 / 17 (Subject to prior change) 75314013.doc Part 7...
  • Page 2 (e.g. condenser-type motors) Screw terminals: Connection: 0.5 – 4 mm² single wire and stranded without ferrule 0.5 – 2.5 mm² stranded wire with ferrule © Gebr. Berker 2005 Version: 10.05.2005 Page: 2 / 17 (Subject to prior change) 75314013.doc Part 7...
  • Page 3 In the manual control mode, only long operation (MOVE) (long depression of key) and the stop command (brief depression of key) are available. © Gebr. Berker 2005 Version: 10.05.2005 Page: 3 / 17 (Subject to prior change) 75314013.doc...
  • Page 4 17 Safety 2 Safety 1 Bit C, W, (R*) For objects marked (R), the current object status can be read out (set "R" flag). © Gebr. Berker 2005 Version: 10.05.2005 Page: 4 / 17 (Subject to prior change) 75314013.doc Part 7...
  • Page 5 • Response after failure and return of bus voltage presettable. • Manual control of the output channels is possible even without bus voltage. The manual control mode can be inhibited. © Gebr. Berker 2005 Version: 10.05.2005 Page: 5 / 17 (Subject to prior change) 75314013.doc...
  • Page 6 (MOVE) depending on the direction of movement. This setting may be required for certain types of drives (please observe the instructions of the motor manufacturers). Even an 'infinite' long operation (MOVE) can be interrupted by a STEP command. © Gebr. Berker 2005 Version: 10.05.2005 Page: 6 / 17 (Subject to prior change) 75314013.doc...
  • Page 7 "No reaction", the corresponding outputs are enabled without starting a new movement. If enabling by "No reaction" occurs during a safety movement still in progress, the outputs are enabled without interrupting the movement. © Gebr. Berker 2005 Version: 10.05.2005 Page: 7 / 17 (Subject to prior change) 75314013.doc...
  • Page 8 • An object update of the safety objects ("ON" after "ON" resp. "OFF" after "OFF") yields no reaction. • Move-step or step-step commands during an active safety function will be rejected. © Gebr. Berker 2005 Version: 10.05.2005 Page: 8 / 17 (Subject to prior change) 75314013.doc...
  • Page 9 (bus voltage available), the actuator executes the parameterized "Response on bus voltage return" when the mains is restored later on. Manual control is not possible. © Gebr. Berker 2005 Version: 10.05.2005 Page: 9 / 17 (Subject to prior change) 75314013.doc...
  • Page 10 Manual control is only possible when mains voltage is available. Depending on the "Manual control on bus voltage failure" parameter on the "Manual control" card, manual control with no bus voltage applied is possible. An activated manual control mode ends on return of bus voltage. © Gebr. Berker 2005 Version: 10.05.2005 Page: 10 / 17 (Subject to prior change) 75314013.doc...
  • Page 11 (stop). A press on the "OFF" key executes the stop function. All relays are switched off immediately. The master stop function is available in the permanent manual control mode only! © Gebr. Berker 2005 Version: 10.05.2005 Page: 11 / 17 (Subject to prior change) 75314013.doc...
  • Page 12 (short depression of key) are possible. When delivered ex factory (actuator not yet programmed), the long operation (MOVE) is factory-adjusted to 'infinite'. After programming of the device with the ETS, the moving time parameterized for each output channel under "Long operation (MOVE)" is applicable. © Gebr. Berker 2005 Version: 10.05.2005 Page: 12 / 17 (Subject to prior change) 75314013.doc...
  • Page 13 • Break during change of movement direction: 1 second • Response after bus voltage failure: stop • Response on return of bus voltage: stop • Manual control: fully enabled © Gebr. Berker 2005 Version: 10.05.2005 Page: 13 / 17 (Subject to prior change) 75314013.doc...
  • Page 14 Stop The shutter moves up again on bus voltage Moving up return. The shutter moves down again on bus Moving down voltage return. © Gebr. Berker 2005 Version: 10.05.2005 Page: 14 / 17 (Subject to prior change) 75314013.doc Part 7...
  • Page 15 Output 2 to 4 in "Mode of operation = 4-channel operation" resp. Output 2/4 in "Mode of operation = 2 x 2-channel operation" see output 1! © Gebr. Berker 2005 Version: 10.05.2005 Page: 15 / 17 (Subject to prior change) 75314013.doc...
  • Page 16 Assignment, outputs 2 to 4 see output 1 resp. output 2/4 Response at the beginning see output 1 and end, outputs 2 to 4 resp. output 2/4 © Gebr. Berker 2005 Version: 10.05.2005 Page: 16 / 17 (Subject to prior change) 75314013.doc Part 7...
  • Page 17 Only with "Manual control" = "Inhibited"! Software information • This type of actuator does not permit read-out of bus voltage by the ETS! © Gebr. Berker 2005 Version: 10.05.2005 Page: 17 / 17 (Subject to prior change) 75314013.doc...