Instructional Leaflet
Effective March 2012

Figure 66. Auxiliary Switch (2A/2B)

Table 9. Auxiliary Switch, Overcurrent Trip Switch and Cell Switch
Contact Ratings
Contact Rating
Control
Inductive Load
Voltages
(amperes)
250 Vac
10
125 Vdc
0.5
250 Vdc
0.25
Table 10. Undervoltage Release
Operational
Control
Voltage Range
Voltages
85-110%
24 Vdc
20-26 Vdc
j
32 Vdc
27-35 Vdc
j
48 Vdc
41-53 Vdc
j
110-125 Vdc
94-138 Vdc
j
220-250 Vdc
187-275 Vdc
j
110-127 Vac
94-140 Vac
k
208-240 Vac
177-264 Vac
k
380-415 Vac
323-457 Vac
k
480 Vac
408-528 Vac
k
600 Vac
510-660 Vac
k
j Required for 200 ms
k Required for 400 ms
50
EATON CORPORATION www.eaton.com
IB2C12063H03
Dropout
j
k
Volts
Inrush/Continuous
30-60%
Power Consumption
7-14 Vdc
250 W/18 W
10-19 Vdc
275 W/15 W
14-29 Vdc
275 W/18 W
33-75 Vdc
450 W/10 W
66-150 Vdc
450 W/10 W
33-76 Vac
450 VA/10 VA
62-144 Vac
400 VA/10 VA
114-249 Vac
480 VA/10 VA
144-288 Vac
400 VA/10 VA
180-360 Vac
400 VA/10 VA
Instructions for Installation, Operation and
Maintenance of Magnum SB Insulated Case
Figure 67. Mechanical Trip Indicator with Associated Overcurrent
Trip Switch

Internal Electrical Accessories

Other electrical accessories are mounted inside the circuit
breaker . They can be factory or site installed . There are two
different internally mounted accessories:
• Overcurrent Trip Switch (Bell Alarm)
• Motor Operator
Overcurrent Trip Switch (Bell Alarm)
An overcurrent trip switch (bell alarm) is an optional device
Opening
Time (ms)
(Figure 67) . It provides an electrical indication when a
circuit breaker trips as a result of the trip unit reacting to an
70
overcurrent condition . Opening as a result of a circuit breaker's
70
manual open button, shunt trip or undervoltage release
70
does not cause the overcurrent trip switch to operate . The
70
overcurrent trip switch has (2a 2b) Form C contacts (Table 9) .