Troubleshooting
4-3-47 COMP Overcurrent error
Outdoor unit display
∙ Will occur if the overcurrent flowing in the IPM.
Judgment Method
∙ Detected by H/W or S/W
∙ COMP. defective.
Cause of problem
∙ Inverter PCB Defective.
1. Cause of problem
Is the outdoor unit installed properly?
Is the resistance value
between phase of Compressor wire
(U-V, V-W, W-U) less than 2Ω?
Is the resistance between
the body of Compressor and
Does the Compressor
connection wire properly connect
to the compressor?
4-74
(INVERTER1 PCB)
(INVERTER2 PCB)
Power Off
Yes
Yes
chassis MΩ?
Yes
Yes
Continue.
No
Remove the obstacles and check
the status of the installation.
No
Replace Compressor
No
Replace Compressor
Check the connection wire
No
(Check the status of the
connection UVW)