Samsung AM080xXV Series Service Manual page 182

Outdoor unit
Table of Contents

Advertisement

Outdoor unit
display
Duct, Cassette (1/2 Way),Console, Celing
Operation Defrost
Indoorunit
×
display
※ ●: ON ◑: Flash ×: OFF
Judgment
Refer to the judgment method below.
Method
Cause of
CCH Connector PCB is not connected / Compressor Top sensor breakaway / Own problem of CCH
problem
1. Judgment Method (2hours after reset or power on, It will be judged once.)
① Compressor Top temperature at the time of judgment - Tini < 2℃ ( ※Tini : Power on or temperature of initial compressor Top after reset )
② Compressor Top temperature at the time of judgment- suction1 temp. sensor < 30℃
③ Outdoor temperature < 30℃
④ UP state
※ If all the conditions are satisfied at the same time : Mark the CCH wire breaking error (E445)
Is the CCH connector connected to PCB?
Is the compressor Top temperature
sensor fixed in correct position?
(500~700 Ω /infinite for disconnection)
Does the E445 error occur even after
the outdoor unit K3" RESET?
Samsung Electronics
( Water Cooled )
Timer
Fan Filter/MPI Operation Defrost
×
Yes
Yes
Is CCH resistance normal?
Yes
Yes
Replace the PCB.
Cassette (4/Mini4 Way)
×
No
No
No
No
Wall-mounted (NeoForte)
Timer
Filter Operation
Connect.
Fix the compressor Top
temperature sensor in
correct position.
Change CCH.
Normal Operation.
Troubleshooting
Timer
Turbo
4-65