4-2. Service Operation

4-2-1 Special Operation

■ AM080/100/120/140/160/180/200/220FSXVSGS
► Key input of the outdoor unit when the service enters the operation mode.
K1 (Number of press)
1 time
2 times
3 times
4 times
5 times
6 times
7 times
8 times
9 times
10 times
11 times
12 times
Press and hold 1 time
K2 (Number of press)
1 time
2 times
3 times
4 times
5 times
6 times
7 times
8 times
9 times
10 times
11 times
12 times
13 times
※ When pcb will be replaced or repaired , please shut off the power after carrying out discharge mode without fail
※ When discharge mode is progressing, DC voltage of inverter PBA 1 & inventer PBA 2 indicate on display alternately.
If LED display of inverter PBA 1 & inventer PBA 2 will be turned off and "OK" is displayed, a discharge is completed.
※ If INV error is occurred(E464/364, E461/361, etc.), please wait more than 15 minutes until self-discharging after shutting off the power
because it can not enter a discharge mode.
※ If normal completion discharge mode or self-discharge will be not completed, it is very dangerous to contact because a high DC voltage of
inverter PBA is charged.
4-2
Key operation
Refrigerant charging in Heating mode
Trial operation in Heating mode
Pump out in Heating mode (Outdoor unit address 1)
Pump out in Heating mode (Outdoor unit address 2)
Pump out in Heating mode (Outdoor unit address 3)
Pump out in Heating mode (Outdoor unit address 4)
Vacuumig (Outdoor unit address 1)
Vacuumig (Outdoor unit address 2)
Vacuumig (Outdoor unit address 3)
Vacuumig (Outdoor unit address 4)
Vacuuming (All outdoor units)
End Key operation
Auto Trial Operation
Key operation
Refrigerant charging in Cooling mode
Trial operation in Cooling mode
Pump down all units in Cooling mode
H/R: Checking the pipe connection
H/P: Automatic setting of operation mode (Cooling/Heating)
for trail operation
Checking the amount of refrigerant
Discharge mode of DC link voltage
Forced defrost operation
Forced oil collection
Inverter compressor 1 check
Inverter compressor 2 check
Fan 1 check
Fan 2 check
End Key operation
Display on segment
K, 1, BLANK, BLANK
K, 2, BLANK, BLANK
K, 3, BLANK, 1
K, 3, BLANK, 2
K, 3, BLANK, 3
K, 3, BLANK, 4
K, 4, BLANK, 1
K, 4, BLANK, 2
K, 4, BLANK, 3
K, 4, BLANK, 4
K, 4, BLANK, A
-
K, K, BLANK, BLANK
Display on segment
K, 5, BLANK, BLANK
K, 6, BLANK, BLANK
K, 7, BLANK, BLANK
K, 8, BLANK, BLANK
"K" "9" X X (Display of last two digits may
differ depending on the progress)
K, A, BLANK, BLANK
K, B, BLANK, BLANK
K, C, BLANK, BLANK
K, D, BLANK, BLANK
K, E, BLANK, BLANK
K, F, BLANK, BLANK
K, G, BLANK, BLANK
-