4-3-34 3-phase Input Wiring error

Outdoor unit
display
Duct, Cassette (1/2 Way),Console, Celing
Operation Defrost
Indoorunit
×
display
※ ●: ON ◑: Flash ×: OFF
. When turn on the power and check the status of the power from the inverter.
If the phase does not connect the power(no phase) : E425 or E466 (E366) is displayed
Judgment
(Air conditioner to maintain the normal state.)
Method
However) N-phase must be properly connected.
∙ Check the input wiring
Cause of
problem
∙ EMI Fuse short
1. Cause of problem
Power Off
Did the Main
Terminal Block and Power R, S, T, N is
connected properly?
Did the Reactor
Connection Terminal is connected
properly?
Did the EMI PCB Fuse is short?
Is EMI PCB CN21
connector and Inverter PCB accurately
connected?
Replace the MAIN PCB.
4-58
Timer
Fan Filter/MPI Operation Defrost
×
Yes
Yes
No
Yes
Cassette (4/Mini4 Way)
Timer
Filter Operation
×
Power BOX Terminal : Check the phase-to-phase
No
connection 380V of the R, S, T and then restart.
(N-phase must be properly connected.)
No
Connection and then restart it
Low voltage error during this initial charge :
No
Replace Fuse, if the rectifier diode of the
Yes
Connection and then restart it
Wall-mounted (NeoForte)
Timer
Turbo
inverter PCB is normal.
Samsung Electronics