Chapter 2
Use a Memory Card Reader
Change the Load
Parameters
30
When you store a project to a memory card, you define:
When to load the project (On Power Up, On Corrupt Memory, User
Initiated).
What mode to set the controller (if the keyswitch is in REM and the
Load mode is not User Initiated).
To assign a project to load from the memory card, edit the Load.xml file on
the card by following the steps that match the numbers in the illustration.
Description
To change the load parameters for a project, use a text editor to open the
XML file with the same name as the project.
Edit the Load Image option of the project.
To set the Load Image option to:
On Power Up
On Corrupt Memory
User Initiated
Edit the Load Mode option of the project (does not apply if the Load Image
option is User Initiated).
To set the Load Mode option to:
Program (Remote Only)
Run (Remote Only)
Rockwell Automation Publication 1756-PM017H-EN-P - February 2018
Then enter:
ALWAYS
CORRUPT_RAM
USER_INITIATED
Then enter:
PROGRAM
RUN