Mitsubishi Electric S Series Manual page 103

Hide thumbs Also See for S Series:
Table of Contents

Advertisement

S series
2-2. Wired remote controller
ERROR CODE
TEMP.
MENU
ON/OFF
BACK
MONITOR/SET
DAY
OPERATION
PAR-21MAA
CLOCK
2-3. Failure mode table (Wireless remote controller/Wired remote controller)
[Output pattern A] Errors detected by indoor unit
Wired remote controller
Wireless remote controller
Beeper sounds/OPERATION INDICATOR
Check code
lamp blinks
(Number of times)
P1
1
P2
2
P9
E6,E7
3
P4
4
P5
5
P6
6
EE
7
P8
8
E4, E5
9
10
11
Fb
12
E0, E3
E1, E2
[Output pattern B] Errors detected by unit other than indoor unit (outdoor unit, etc.)
Wired remote controller
Wireless remote controller
Beeper sounds/OPERATION INDICATOR
Check code
lamp blinkes
(Number of times)
E9
1
UP
2
U3,U4
3
UF
4
U2
5
U1,Ud
6
U5
7
U8
8
U6
9
U7
10
U9,UH
11
12
13
Others
14
*1 If the beeper does not sound again after the initial two beeps to confirm the self-check start signal was received and the OPERATION INDICATOR lamp does not come on,
there are no error records.
*2 If the beeper sounds three times continuously "beep, beep, beep (0.4 + 0.4 + 0.4 sec.)" after the initial two beeps to confirm the self-check start signal was received, the
specified refrigerant address is incorrect.
• On wireless remote controller
The continuous buzzer sounds from receiving section of indoor unit.
Blink of operation lamp
• On wired remote controller
Check code displayed in the LCD.
ERROR CODE
ON/OFF
FILTER
CHECK
TEST
ERROR CODE
CLEAR
Intake sensor error
Pipe (TH2) sensor error
Pipe (TH5) sensor error
Indoor/outdoor unit communication error
Drain sensor error/Float switch connector open
Drain pump error
Freezing/Overheating protection operation
Communication error between indoor and outdoor units
Pipe temperature error
Remote controller signal receiving error
Indoor unit control system error (memory error, etc.)
Remote controller transmission error
Remote controller control board error
Indoor/outdoor unit communication error (Transmitting error) (Outdoor unit)
Compressor overcurrent interruption
Open/short of outdoor unit thermistors
Compressor overcurrent interruption (When compressor locked)
Abnormal high discharging temperature/49C worked/insufficient refrigerant
Abnormal high pressure (63H worked)/Overheating protection operation
Abnormal temperature of heatsink
Outdoor unit fan protection stop
Compressor overcurrent interruption/Abnormal of power module
Abnormality of super heat due to low discharge temperature
Abnormality such as overvoltage or voltage shortage and abnormal synchronous
signal to main circuit/Current sensor error
Other errors (Refer to the technical manual for the outdoor unit)
Turn on the power.
Press the [CHECK] button twice.
Set address with [TEMP] button if system control is used.
Press the [ON/OFF] button to stop the self-check.
CHECK button
Address
TEMP. button
IC : Indoor unit
OC: Outdoor unit
– – – – : No trouble generated in the past.
Check code
F F F F : No corresponding unit.
Unit No.
Timer ON/OFF button
<To cancel check code>
Display the error code on the self-check result display screen.
The address for self-check will blink when the
button is pressed twice within three seconds.
Symptom
Symptom
OUTDOOR UNIT
ON/OFF
Remark
Remark
For details, check the LED display
of the outdoor controller board.
B-103