Siemens CC-2M Directions For Use Manual page 55

Table of Contents

Advertisement

Available languages

Available languages

7XV5662-0AD00
– Fast Transient Surge Withstand Capability
IEEE C37.90.1
– Radiated Electromagnetic Interference
IEEE C37.90.2
– Damped Oscillations
IEC 60694, IEC 61000-4-12
EMC Tests For Noise Emission (Type Test)
Standard:
– Radio Noise Voltage and Current
to Lines
IEC-CISPR 22
– Radio Noise Field Strength
IEC-CISPR 22
– Voltage fluctuations and flicker
on the mains power input at AC 230 V
IEC 61000–3–3
Mechanical Stress Tests
Vibration and Shock Stress During Operation
Standards:
– Vibration
IEC 60255-21-1, Class 2
IEC 60068-2-6
– Shock
IEC 60255-21-2, Class 1
IEC 60068-2-27
C53000-B1174-C205-1
4 kV; 5/50 ns; 5 kHz; burst length = 15 ms;
repetition rate 300 ms; both polarities;
= 50 Ω; test duration 1 min
R
i
35 V/m; 25 MHz to 1000 MHz
2.5 kV (Peak Value), polarity alternating
100 kHz, 1 MHz, R
i
EN 61000-6-3 (Generic Standard)
150 kHz to 30 MHz
Limit Class B
30 MHz to 1000 MHz
Limit Class B
Limits are maintained
IEC 60255–21 and IEC 60068–2
Sinusoidal
10 Hz to 60 Hz: ± 0.075 mm Amplitude
60 Hz to 150 Hz: 1 g acceleration
frequency sweep rate 1 Octave/min
20 cycles in 3 orthogonal axes.
Half-sine shaped
acceleration 5 g, duration 11 ms,
3 shocks in each direction of
3 orthogonal axes