Description; Standard Configurations - ABB RELION 615 SERIES Product Manual

Voltage protection and control
Hide thumbs Also See for RELION 615 SERIES:
Table of Contents

Advertisement

Voltage Protection and Control
REU615
Product version: 5.0 FP1

1. Description

The voltage protection and control relay REU615 is available in
two standard configurations, denoted A and B. Configuration A
is preadapted for voltage and frequency-based protection
schemes in utility and industrial power systems and distribution
systems including networks with distributed power generation.
The B configuration is designed for automatic voltage
regulation of power transformers equipped with an on-load tap
changer. Both configurations also feature additional CB
control, measuring and supervising functions. REU615 is a
member of ABB's Relion
protection and control product series. The 615 series relays are
characterized by their compactness and withdrawable-unit
design.
Re-engineered from the ground up, the 615 series has been
designed to unleash the full potential of the IEC 61850 standard
for communication and interoperability between substation
automation devices. Once the standard configuration relay has
been given the application-specific settings, it can directly be
put into service.
The 615 series relays support a range of communication
protocols including IEC 61850 with Edition 2 support, process
bus according to IEC 61850-9-2 LE, IEC 60870-5-103,
ABB
®
product family and part of its 615
®
Modbus
and DNP3. Profibus DPV1 communication protocol is
supported by using the protocol converter SPA-ZC 302.

2. Standard configurations

REU615 is available in two standard configurations. The
standard signal configuration can be altered by means of the
signal matrix or the graphical application functionality of the
Protection and Control IED Manager PCM600. Further, the
application configuration functionality of PCM600 supports the
creation of multi-layer logic functions using various logical
elements, including timers and flip-flops. By combining
protection functions with logic function blocks, the relay
configuration can be adapted to user-specific application
requirements.
The relay is delivered from the factory with default connections
described in the functional diagrams for binary inputs, binary
outputs, function-to-function connections and alarm LEDs.
Some of the supported functions in REU615 must be added
with the Application Configuration tool to be available in the
Signal Matrix tool and in the relay. The positive measuring
direction of directional protection functions is towards the
outgoing feeder.