Voltage Protection and Control
REU615
Product version: 5.0 FP1
Measurement functions
Table 61. Three-phase current measurement (CMMXU)
Characteristic
Operation accuracy
Suppression of harmonics
Table 62. Sequence current measurement (CSMSQI)
Characteristic
Operation accuracy
Suppression of harmonics
Table 63. Three-phase voltage measurement (VMMXU)
Characteristic
Operation accuracy
Suppression of harmonics
Table 64. Residual voltage measurement (RESVMMXU)
Characteristic
Operation accuracy
Suppression of harmonics
Table 65. Sequence voltage measurement (VSMSQI)
Characteristic
Operation accuracy
Suppression of harmonics
ABB
Value
Depending on the frequency of the measured current: f
±0.5% or ±0.002 × I
n
(at currents in the range of 0.01...4.00 × I
DFT: -50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
RMS: No suppression
Value
Depending on the frequency of the measured current: f/f
±1.0% or ±0.002 × I
n
at currents in the range of 0.01...4.00 × I
DFT: -50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
Value
Depending on the frequency of the voltage measured: f
At voltages in range 0.01...1.15 × U
±0.5% or ±0.002 × U
n
DFT: -50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
RMS: No suppression
Value
Depending on the frequency of the measured voltage: f/f
±0.5% or ±0.002 × U
n
DFT: -50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
RMS: No suppression
Value
Depending on the frequency of the voltage measured: f
At voltages in range 0.01...1.15 × U
±1.0% or ±0.002 × U
n
DFT: -50 dB at f = n × f
, where n = 2, 3, 4, 5,...
n
1MRS757058 K
±2 Hz
n
)
n
= ±2 Hz
n
n
±2 Hz
n
n
= ±2 Hz
n
±2 Hz
n
n
39