baltur BT 300 DSG 4T Manual User Instructions page 49

Two stage diesel burners
Hide thumbs Also See for BT 300 DSG 4T:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 30
Burner does not start
Poor flame, with sparks
Poorly shaped flame with
smoke and soot
Defective flame (flickering or
protruding from combustion
head)
Corrosion inside the boiler
Soot at the mouth of the
chimney
Thermostats (boiler or room) or pressure switches
are open
Photocell short-circuit
There is no voltage because of the an open contact
in the main switch or the meter overload-release,
or no voltage in the line
Thermostat line not wired
according to diagram or open thermostats
Equipment internal fault
Spraying pressure is too low
Too much combustion air
Nozzle inefficient because dirty or worn
Water in the fuel
Insufficient combustion air flow
Nozzle inefficient because dirty or worn
Combustion chamber unsuitably designed or too
small
Nozzle capacity too low with respect to combustion
chamber volume
Unsuitable or excessive refractory lining
Boiler or chimney ducts blocked.
Spraying pressure is low
Excessive draught (only when there is an extractor
in the chimney)
Nozzle inefficient because dirty or worn
Water in the fuel
Disc fouled
Excess combustion air
Air passage between disk and blast tube
Boiler operating temperature too low (below the
dew point)
High percentage of sulphur in the fuel
Too low flue gas temperature (below 180 °C)
Excessive cooling (below 180°C) of smoke before
exit outflow, for an outside chimney not adequately
heat insulated or cold air infiltration
0006081081_201406
Raise their settings, or wait until pressure
or temperature values naturally decrease
to close them
Replace it
Activate switches or wait for power to return
Check connections and thermostats
Replace it
Reset at proper value
Reduce combustion air flow
Clean or replace
Remove it from the tank using a suitable
pump (never use the burner pump for this
job). (Never use the burner pump for this job)
Increase combustion air
Clean or replace
Modify or reduce the nozzle capacity with
respect to the combustion chamber or
replace the boiler
Increase nozzle flow by replacing
M o d i f y i t a c c o r d i n g t o t h e b o i l e r
manufacturer's instructions
Arrange for cleaning
Raise pressure to the prescribed value
Adjust the suction fan speed by changing
the pulley diameter
Clean or replace
Remove it from the tank with a suitable pump
(never use the burner pump for this job)
Clean it
Reduce combustion air
Correct the position of the combustion head
regulating device
Increase operating temperature
Change the type of fuel
Increase nozzle flow by replacing
Improve insulation and close any opening
letting cold air in
21 / 26