2.2.3
Block Diagram
2.3
WISE-S231
2.3.1
I/O Specifications
Temperature Sensor Input
Operating Range: -25°C ~ 70°C (-4°F ~ 157.9°F)
Data Resolution: 0.1 (°C/°F/K)
Accuracy: ±1.0°C (Vertical Installation)
Update Rate: Minimum 1 second
Response Time: 15 seconds (Achieving 63% of a step function)
Long Term Drift: 0.05°C/Year (0.09°F/Year)
Humidity Sensor Input
Operating Range: 10~90% RH
Resolution: 0.1% RH
Accuracy:
–
±4% for 0%~50% RH
–
±6% for 50%~60% RH
–
±10% for 60%~90% RH
Update Rate: Minimum 1 second
Response Time: 10 seconds (Achieving 63% of a step function)
Long Term Drift: 0.5% RH/Year
Figure 2.2 WISE-4210-AP Block Diagram
17
WISE-4210 Series User Manual