HOTEL SOLUTION™
Room operator unit
Room unit to operate individual room control systems in hotel rooms
• Displays room temperature setpoint and setpoint adjustment
• Individual setpoint adjustment with "plus" and "minus" membrane switches
• Individual manual fan-speed selection for fan control (up to 3 speeds) or
selection of "Auto" operating mode
• Measurement of room temperature with a built-in or externally connected
temperature sensor
The HTC3.2 operator unit for control of indoor room conditions is used in conjunction
with the HRC3.1/HRC3.2 room controllers. The room operator unit detects the
temperature and transmits it to the HRC3.1/HCR3.2 room controllers for room
temperature control. The room operator unit displays the operating mode in the hotel
room and can be used to operate the fan coil unit, either manually or automatically via
the connected room controller.
6
HTC3.2/..
Building Technologies
320

Advertisement

loading

Summary of Contents for Siemens HOTEL SOLUTION HTC3.2 Series

  • Page 1 HOTEL SOLUTION™ HTC3.2/.. Room operator unit Room unit to operate individual room control systems in hotel rooms • Displays room temperature setpoint and setpoint adjustment • Individual setpoint adjustment with "plus" and "minus" membrane switches • Individual manual fan-speed selection for fan control (up to 3 speeds) or selection of "Auto"...
  • Page 2 Function The HTC3.2 room operator unit communicates with the HRC3.1 or HRC3.2 room controller via a serial port, performing the following functions: • Displays the room temperature setpoint • Transmits the manual room temperature setpoint adjustment • Displays the manual room temperature setpoint adjustment •...
  • Page 3 Mechanical design The room operator unit comprises: • Printed circuit board with the electronic circuit, LCD display, buttons for operation, with terminal block and DIP switches • Base frame: − Bticino Living/Type L4703 for HTC3.2/BB − Bticino Light/Type N4703 for HTC3.2/BW −...
  • Page 4 The guest can use the room unit to do the following: • Adjust the preset room temperature setpoint by ±2 K or by ±4 K in eight steps. The step size of 0.5 or 1.0 K can be configured in the room controller. The eight temperature-change increments are indicated by a horizontal scale across the center of the LCD display panel.
  • Page 5 Engineering notes The room unit is designed for flush wall mounting in conjunction with base-frames and Base frame cover plates from various manufacturers: • Bticino Living for HTC3.2/BB • Bticino Light for HTC3.2/BW • Vimar Idea for HTC3.2/VB • Vimar Plana or Ikon for HTC3.2/VW Up to 4 room units may be connected to one room controller.
  • Page 6 Slave On/Off In a control loop with several room units, the temperature is measured in one device only (the master). The LS flag (SL = 0) determines whether the room unit should measure the temperature, or whether it is a slave device (SL = 1), in which case the temperature sensor is disabled.
  • Page 7 Correcting the If the sensor is in an unsuitable location, the measured value can be corrected with a measured value temperature offset. The correction can be undertaken with the SCOPE or HSC (Hotel Solution Commissioning) tool. In the standard application the basic setting for the temperature offset is –4 K. This applies to the room operator unit in cases where the temperature is measured with the internal room sensor.
  • Page 8 Operating notes Alarm messages Pattern Description All symbols OFF No supply voltage to the HTC3.2 Possible causes: − Room controller off or faulty − Bus cable not correctly connected, or connection broken − HTC3.2 faulty All symbols No communication with the room controller flashing (2 Hz) Possible causes: −...
  • Page 9 Installation Suitable for flush mounting in rectangular 3 modules flush-mounting box or rounded hollow wall HTC3.2/BB and HTC3.2/BW Bticino 503E (angular),PS563N (round) HTC3.2/VB and HTC3.2/VW Vimar V71613 (round), V71304 (angular) Color Operator panel Pantone black 7U2Y HTC3.2/BB – Bticino frame L4703 Dimensions 115 mm x 72 mm x 25 mm HTC3.2/BW –...
  • Page 10 HTC3.2/VB Dimensions in mm 111,8 90,6 Note See the frame supplier documentation for dimensions of other frames and hole spacing (Bticino, Vimar). 10/10 © 2006-2008 Siemens Switzerland Ltd Subject to change Building Technologies HTC3.2/.. - Room operator unit CM2N6320en 01.09.2008...