Siemens HLIM Installation Instructions
Siemens HLIM Installation Instructions

Siemens HLIM Installation Instructions

Loop isolator module

Advertisement

Installation Instructions
Model HLIM
Loop Isolator Module

OPERATION

INSTALLATION

Class B
P/N 315-033170-2
The SIEMENS Model HLIM Loop Isolator Module isolates short circuits on FireFinder-
XLS analog loops. By placing devices between HLIMs during installation, a short in
the wiring within that group is disconnected from the rest of the loop. The remainder
of the devices continue
to operate. The HLIM
operates in both Class A
and Class B circuits.
A yellow LED flashes
when a device detects a
short circuit. The HLIM
then isolates that part of
the loop. When the short
is removed, the HLIM
automatically restores
the loop to normal
operation. The HLIM
does not have a loop address and therefore does not require address programming
nor does it reduce the loop capacity below 252 devices.
Remove all system power before installation, first the battery and then the AC.
The HLIM is a polarity insensitive module. Refer to Figure 1 for the location of the
two input terminals and two output terminals. Line 1 and Line 2 can be either line of
the loop.
The HLIM may be used in two circuit configurations as follows:
(See Figure 2) In Class B wiring each HLIM isolates a branch on the circuit. Note that
a short on the main branch causes the entire loop to fail. To prevent this, mount the
HLIMs at the FireFinder-XLS enclosure and run each branch independently.
FRONT
FAULT
Figure 1
The HLIM-1 Loop Isolator Module
Siemens Building Technologies
BACK
IN - LINE 1
IN - LINE 2
OUT - LINE 1
OUT - LINE 2
Fire Safety

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the HLIM and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Siemens HLIM

  • Page 1 The HLIM may be used in two circuit configurations as follows: Class B (See Figure 2) In Class B wiring each HLIM isolates a branch on the circuit. Note that a short on the main branch causes the entire loop to fail. To prevent this, mount the HLIMs at the FireFinder-XLS enclosure and run each branch independently.
  • Page 2 IN OUT OUT 7 . Refer to DLC Installation Instructions, P/N 315-033090 for the list of compatible devices. Figure 3 8. All terminals are power limited. HLIM Wiring Diagram - Class A Installation (Single Loop) Siemens Building Technologies P/N 315-033170-2 Fire Safety...
  • Page 3 Use a standard 3 1/2-inch deep, double gang electrical switchbox or a 4-inch square electrical box that is 2 1/8 inches deep. • Connect the field wiring. Press the HLIM into the box and fasten the module plate to the box. •...
  • Page 4 Siemens Building Technologies, Inc. Siemens Building Technologies, Ltd. 8 Fernwood Road 2 Kenview Boulevard Florham Park, New Jersey 07932 Brampton, Ontario L6T 5E4 P/N 315-033170-2...

Table of Contents