Installation Instructions
Model HLIM
Loop Isolator Module
OPERATION
Figure 1
HLIM-1 Module
ELECTRICAL RATINGS
INSTALLATION
DOUBLE GANG BOX
3 1/2-INCHES DEEP
4-INCH SQUARE BOX
2 1/8-INCHES DEEP
SWITCHPLATE
5-INCHES SQUARE
(SUPPLIED)
Figure 2
Mounting the HLIM
P/N 315-034904-4
The Model HLIM Loop Isolator Module from Siemens Industry, Inc. isolates short
circuits on FireFinder-XLS or FS-250 analog loops. By placing devices between HLIMs
during installation, a short in the wiring within that group is disconnected from the
rest of the loop. The remainder of the devices continue to operate. The HLIM oper-
ates in both Class A and Class B circuits.
A yellow LED flashes when a device detects a short circuit. The HLIM then isolates
that part of the loop. When the short is removed, the HLIM automatically restores the
loop to normal operation. The HLIM does not have a loop address and therefore does
not require address programming nor does it reduce the loop capacity below 252
devices.
Remove all system power before installation, first the battery and then the AC.
D
L
C
/
M
a
. x
C
r u
e r
t n
The HLIM is a polarity insensitive module. Refer to Figure 1 for the location of the
two input terminals, two output terminals and earth ground. Line 1 and Line 2 can be
either line of the loop.
Terminal Number
Description
1
In — Line 1
2
In — Line 2
3
Out — Line 1
4
Out — Line 2
5
Earth Ground
Mechanical Installation (See Figure 2)
• Use a standard 3 1/2-inch deep, double gang electrical
switchbox or a 4-inch square electrical box that is 2 1/8 inches
deep.
• Connect the field wiring. Press the HLIM into the box and
fasten the module plate to the box.
SWITCHPLATE
5-INCHES SQUARE
(SUPPLIED)
• Cover the module front plate with the plate supplied and
fasten with screws supplied.
F
S
D -
L
C
L
o
o
p
1
m
A
Building T T T T T ec
Building
Building
Building
Building
Siemens
Siemens Industry
Siemens
Industry
Industry
Industry, , , , , Inc.
Siemens
Siemens
Industry
ec
ec
echnologies Di
ec
hnologies Division
hnologies Di
hnologies Di
hnologies Di
vision
vision
vision
vision
Inc.
Inc.
Inc.
Inc.

Advertisement

loading

Summary of Contents for Siemens HLIM

  • Page 1 ELECTRICAL RATINGS INSTALLATION The HLIM is a polarity insensitive module. Refer to Figure 1 for the location of the two input terminals, two output terminals and earth ground. Line 1 and Line 2 can be either line of the loop.
  • Page 2 The HLIM may be used in two circuit configurations as follows: Class B (See Figure 3) In Class B wiring each HLIM isolates a branch on the circuit. Note that a short on the main branch causes the entire loop to fail. To prevent this, mount the HLIMs at the enclosure and run each branch independently.