Advertisement

Configuring
5.1 Setup and connection
6. Parameterize the CP 343-2 P AS-Interface master module and the AS-Interface slaves in
HW Config. For a detailed description of parameterizing the modules, see:
– Documentation for the corresponding AS-Interface slaves
You can use the "Load into the PG" function to import the configuration of the AS-Interface
slaves into your hardware configuration:
Figure 5-1
7. Link the function block to the SIMOTION project (refer to Chapter Integrating the
_ASI_cmdInterface function block and the application examples in the user project
(Page 17)).
Distributed use of the DP/AS-Interface Link 20E/Link Advanced AS-Interface master module
(SIMOTION C2xx, SIMOTION P350, and SIMOTION D4xx)
1. Assemble and install the cables for the DP/AS-Interface Link 20E/Link Advanced AS-
Interface master module. Install the cables and address the AS-Interface slaves.
2. Establish the PROFIBUS connection between the DP/AS-Interface Link 20E/
Link Advanced and the SIMOTION device.
3. Set the PROFIBUS DP node address on the DP/AS-Interface Link 20E/Link Advanced.
4. Switch on the terminating resistor at the first and last bus node.
Note
Steps 1. to 4. are described in detail in the
SIMATIC NET DP/AS-Interface Link Advanced Manuals.
5. Add the DP/AS-Interface Link 20E/Link Advanced AS-Interface master module to the
SIMOTION project (see Chapter Adding the AS-Interface master modules to the SIMOTION
project (Page 30)).
28
SIMATIC NET CP 343-2/CP 343-2 P AS-Interface Master Manual.
Loading the AS-Interface slave configuration into the PG
SIMATIC NET DP/AS-Interface Link 20E and
Extension to the command interface for AS-Interface master modules
Function Manual, 01/2015