8.5.
Electrical Work
• • • • Always use at the rated voltage and with a specific air conditioning circuit.
• • • • Some installation locations may require the installation of a short circuit breaker.
• • • • A 16 Ampere time delay fuse or circuit breaker is required.
• • • • Nominal cross sectional area of power supply wire must be 3 core x 1.0 mm
• • • • The power supply must be from an independent circuit.
• • • • All electrical installation must be made in accordance with local wiring and safety regulations wherever applicable.
• • • • There must be a double pole switch with a minimum of 3 mm contact gap in the fixed installation circuit.
• • • • Please consult your dealer concerning installation requirements.
Note: These equipment shall be connected to a suitable mains network with a main impedance less then the following:-
CW-A90VE: 0.40Ω CW-A120VE: 0.30Ω
8.6.
Condensed Water Drainage
In order to drain off the condensed water, it is recommended
that you install a drain pan using the folowing procedure.
1. Slide the chassis out from the cabinet.
2. Install the drain pan.
Install the drain pan at the left corner of the cabinet.
2
or above.
3. Connect the drain hose.
Bottom side view with drain pan.
NOTE
Drain hose or tubing can be purchased locally to satisfy
your particular needs.
4. Slide the chassis back into the cabinet.