2. Procedure to Remove Outdoor Unit Fan and Fan
Motor
Procedure
Step
∗ Remove the front piping
cover, etc., according to the
procedure for removing the
external casing.
Remove the 4 screws
1
and disconnect the 8
tabs fastening the air
discharge grille on the
top/bottom and left/
right, and remove the
air discharge grille.
Remove the fan clamp
2
fastening the propeller
fan; remove the nut and
washer.
3
Disconnect the motor
connector from the
PCB's wiring connector,
and remove the
condenser.
Removal Procedure
Warning
Be sure to wait for 10 minutes or more after turning off all power
supplies before disassembling work.
Procedure

Procedure to Remove Outdoor Unit Fan and Fan Motor

Connector
Condenser
Points
Note:
The fan motor's lead wire
cannot be disconnected as is.
You must first remove the screw
on the right side of the front
casing (1).