Honeywell VR4304 Series Manual
Honeywell VR4304 Series Manual

Honeywell VR4304 Series Manual

Intermittent pilot combination gas control

Advertisement

These intermittent pilot gas controls are used in gas-fired
appliances with capacities up to 300 feet
wc pressure drop [8.5 meters
gas. They include a manual valve, two automatic operators,
a pressure regulator, pilot adjustment and a conduit cover.
See Table 1 for temperature ranges and regulator types.
CAPACITY:
Size
(Inlet x Outlet)
1/2 x 1/2
1/2 x 3/4
3/4 x 3/4
a
Capacity based on 1000 Btu/feet
gravity natural gas at 0.25 kPa pressure drop].
TABLE 1—TEMPERATURE RANGES AND
REGULATOR TYPES.
Ambient
Model
Temperature
Number
Range
VR4304H
0° F to 175° F
[-18° C to +79° C]
VR4304M
-40° F to 175° F
[-40° C to +79° C]
VR4304P
-40° F to 175° F
[-40° C to +79° C]
Use conversion factors in Table 2 to convert capacities
for other gases.
TABLE 2—GAS CAPACITY CONVERSION FACTORS.
Specific
Gas
Gravity
Manufactured
Mixed
Propane
Combination Gas Control
Application
3
/hour at 1 inch
3
/hour at 0.25 kPa] for natural
Capacity (at 1 inch
wc pressure drop)
3
240 feet
/hour
3
[6.8 meter
/hour]
3
270 feet
/hour
3
[7.6 meter
/hour]
3
300 feet
/hour
3
[8.5 meter
/hour]
3
, 0.64 specific gravity natural gas at 1 inch wc pressure drop [37.3 MJ/meter
Regulator
Type
Slow-opening
Standard-opening
Step-opening
Multiply Listed
Capacity By
0.60
0.516
0.70
0.765
1.53
1.62
J.D. • Rev. 1-94 • ©Honeywell Inc. 1994 • Form Number 69-0695—2
Intermittent Pilot
BODY PATTERN: Straight-through.
INLET X OUTLET SIZES AVAILABLE: 1/2 x 3/4 inch
and 3/4 x 3/4 inch.
ADAPTERS: Adapters available for 1/2 and 3/4 inch
straight and angle connections. Refer to Table 3.
ELECTRICAL RATINGS:
Voltage and Frequency: 120 Vac, 60 Hz.
Current Draw: 0.14A.
Minimum
a
Regulated Capacity
3
30 feet
/hour
[0.8 meter
3
30 feet
/hour
[0.8 meter
3
30 feet
/hour
3
0.8 meter
TABLE 3—ADAPTER (FLANGE) PART NUMBERS.
Inlet/
Outlet
Pipe Size
1/2 inch NPT
3/4 inch NPT
NOTE: Flange Kits include one flange with attached O-ring
and four mounting screws.
APPROVALS:
American Gas Association design certificate:
L2025007.
Canadian Gas Association design certificate:
L2025007.
Australian Gas Association design certificate:
Applied for.
Delta C.
1
VR4304
Regulated Capacity
340 feet
3
/hour]
[9.6 meter
370 feet
3
/hour]
[10.5 meter
415 feet
/hour]
[11.8 meter
Without
Flange
Hex
Type
Wrench
Straight
393690-6
Elbow
393690-3
Straight
393690-4
Elbow
393690-5
Maximum
3
/hour
3
/hour]
3
/hour
3
/hour]
3
/hour
3s
/hour]
3
, 0.64 specific
Part Number
With
Hex
Wrench
393690-16
393690-13
393690-14
393690-15
69-0695—2

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the VR4304 Series and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Honeywell VR4304 Series

  • Page 1 Canadian Gas Association design certificate: Specific Multiply Listed L2025007. Gravity Capacity By Australian Gas Association design certificate: Applied for. Manufactured 0.60 0.516 Delta C. Mixed 0.70 0.765 Propane 1.53 1.62 J.D. • Rev. 1-94 • ©Honeywell Inc. 1994 • Form Number 69-0695—2 69-0695—2...
  • Page 2: Installation

    To convert a gas control from natural to LP gas or from 4. After installation is complete, use these instructions LP to natural gas, contact your Honeywell representative. to check out product operation. Convert standard or slow opening gas controls from...
  • Page 3 LOCATION The combination gas control is mounted in the appli- Fig. 2—Install sediment trap. ance vestibule on the gas manifold. If this is a replacement DROP installation, mount the gas control in the same location as PIPED the old control. HORIZONTAL CONTROL Do not locate the gas control where it can be affected by...
  • Page 4 5. Remove seals over gas control inlet and outlet if necessary. Fig. 4—Top view of gas control. 6. Connect pipe to gas control inlet and outlet. Use wrench on the square ends of the gas control. If a flange is used, place wrench on flange rather than on gas control.
  • Page 5: Startup And Checkout

    2. When the gas control is installed external to the 4. Make sure the conduit cover is in position and se- appliance, install the conduit cover on the conduit fitting. cured to the gas valve with the screw provided. See Fig. 1. Do not secure the conduit cover at this time.
  • Page 6 ADJUST THE PILOT BURNER FLAME Standard-Opening and Slow-Opening Pressure Regulator The pilot flame should envelop 3/8 to 1/2 in. [10 to 13 mm] 1. The gas control outlet pressure should match the of the igniter-sensor tip. Refer to Fig. 8. To adjust the pilot manifold pressure listed on the appliance nameplate.
  • Page 7: Maintenance

    Such heavy cycling can wear out the contact your Honeywell sales representative to request a gas control in one to two years. gas control with corrosion resistant construction.
  • Page 8 The gas control should be replaced if: INSTRUCTIONS TO THE HOMEOWNER (FOR • It does not perform properly on checkout or YOUR SAFETY, READ BEFORE OPERATING) troubleshooting. WARNING • The gas control knob is hard to turn or push down, or it fails to pop back up when released.
  • Page 9: Turning Off The Appliance

    The pilot flame is lit automatically. Do not attempt to 8. Replace the gas control access panel. manually light the pilot. If the appliance does not turn on 9. Reconnect all electric power to the appliance. when the thermostat is set several degrees above room 10.
  • Page 10 Home and Building Control Home and Building Control Helping You Control Your World Honeywell Inc. Honeywell Limited—Honeywell Limitée 1985 Douglas Drive North 740 Ellesmere Road Golden Valley, MN 55422 Scarborough, Ontario M1P 2V9 QUALITY IS KEY 69-0695—2 Printed in U.S.A.

This manual is also suitable for:

Vr4304hVr4304mVr4304p

Table of Contents