APPLICATION

The V4062 Gas Valve Actuator in combination with a V5055,
a
VE5000
or V5097 Gas Valve provides three-position control
of the gas supply to commercial and industrial burners.

FEATURES

• When energized, the V4062 Actuator opens the
V5055/VE5000/V5097 Gas Valve to the low-fire
position. The actuator opens the valve to the fully open
position when the line voltage contacts are made.
a
VE5000 is a European manufactured and approved valve for
European use only.
® U.S. Registered Trademark
Copyright © 2001 Honeywell • All Rights Reserved
HI-LO-OFF Fluid Power
Gas Valve Actuator
• When used with the V5055, V5097 or VE5000
Valve, the combination is rated for final safety shutoff
service.Although the V4062 can be used with all V5055
or V5097 Valve models, the V5055/V5097B with
characterized guide is recommended for optimum
control and low-fire repeatability.
• The standard model has an opening time of
26 seconds at 60 Hz, or 32 seconds at 50 Hz. A
fast-opening model is available, with timings of
13 seconds at 60 Hz, or 16 seconds at 50 Hz.
• Maximum closing time is one second, which meets
code, standard, insurer requirements.
• Damper shaft models are available with or without
spring return; shaft extends out both sides and rides
in Delrin bushings; used with standard damper crank
arm (part no. 7616BR).
• Red OPEN indicator attached to the actuator stem
shows when the valve is even slightly open; yellow
SHUT indicator on the valve stem shows only when
the gas valve is fully closed.
• Ambient temperature range is -40° to 150°F (-40° to
66°C) for 60 Hz models; -10° to 158°F (23° to 70°C) for
50 Hz and 50/60 Hz models.
• Models available with factory adjusted, field-
adjustable, single-pole-double throw (spdt) auxiliary
switch rated at 1/2 hp (0.37 kW). Auxiliary switch can
be added in the field.
• Low-fire position is adjustable with adjusting wrench,
part no. 135796 (included with the actuator).
• Standard enclosure meets NEMA 1 (IP30) general
purpose requirements.
• V4062/V5055C,E and V4062/V5097C,E combinations
available with a proof-of-closure switch and double
valve seal (valve seal overtravel interlock) to meet
specific code/standard/insurer requirements.
• Model available to be used with series 60 floating type
controller.
• Model available with adjustable maximum flow switch.
Application ........................................................................
Features ...........................................................................
Specifications ...................................................................
Ordering Information ........................................................
Installation ........................................................................
Wiring ...............................................................................
Adjustments ......................................................................
Operation ..........................................................................
Service and Checkout ......................................................
V4062A,B,D
PRODUCT DATA
a
Gas
Contents
60-2099-9
1
1
2
2
4
6
7
8
8

Advertisement

Table of Contents
loading

Summary of Contents for Honeywell V4062A

  • Page 1: Table Of Contents

    VE5000 is a European manufactured and approved valve for Contents European use only. Application ................ Features ................Specifications ..............Ordering Information ............Installation ................ Wiring ................Adjustments ..............Operation ................Service and Checkout ............® U.S. Registered Trademark Copyright © 2001 Honeywell • All Rights Reserved 60-2099-9...
  • Page 2: Specifications

    Honeywell, 1885 Douglas Drive North Minneapolis, Minnesota 55422-4386 (800) 328-5111 In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9. International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
  • Page 3 V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR Table 4. Pressure Ratings of Valve-Actuators Combinations. V4062A,D Actuator V4062B Actuator Differential Closeoff Differential Closeoff Valve mbar mbar V5055A,C; V5097A,C 3/4 to 3 in. 1000 V5055A,C 4 in. V5055B, V5097B 3/4 to 3 in.
  • Page 4: Installation

    V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR 6-3/4 (172) KNOCKOUT FOR 1/2 INCH CONDUIT (4) 3-23/32 (95) 5 (127) 27/32 (21) 1-9/32 (33) VALVE VALVE ALLOW 4 INCH (102 MM) CLEARANCE FOR ACTUATOR REMOVAL. M17755 Fig. 1. Approximate mounting dimensions of V4062 Actuators in in. (mm).
  • Page 5 V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR Install Valve The actuator is installed directly on the V5055/V5097 body after the valve is installed in the gas supply line. Refer to the instructions packed with the V5055/V5097 Gas Valve for installation details. When installing the valve, assure that: 1.
  • Page 6: Wiring

    V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR Mount and Adjust 7616BR Damper Crank Arm (If Used) The damper crank arm provides a maximum travel of FIRING 2-5/16 in. (58.7 mm) through a stroke of 52 degrees. RATE CONTROLLER See Fig. 3. If the V4062 has a damper shaft return spring, dampers go to the closed position when power is interrupted by the programmer.
  • Page 7: Adjustments

    V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR ADJUSTMENTS Recommended Procedure To adjust the low-fire setting without energizing the actuator, proceed as follows: Low-Fire Adjustment 1. Remove the wiring compartment cover. The low-fire position is adjustable from 0.16 in. to 0.64 in.
  • Page 8: Operation

    V4062A,B,D HI-LO-OFF FLUID POWER GAS VALVE ACTUATOR OPERATION See Specifications section for further specifications. To function as intended, the V4062 must be connected to a OUTDOOR properly sized valve. Too large a valve will not properly control SENSOR the gas flow.

This manual is also suitable for:

V4062bV4062d

Table of Contents