Specifications - Siemens OpenAir GDE Series Technical Instructions

Non-spring return rotary 24 vac floating control electric damper actuator
Hide thumbs Also See for OpenAir GDE Series:
Table of Contents

Advertisement

Technical Instructions
Document No. 155-188P25
December 26, 2007

Specifications

Power supply
Equipment rating
Auxiliary features
Function
Mounting
Housing
Page 2
Operating voltage (G–Y1 or G–Y2)
Frequency
Power consumption
Rating
Feedback potentiometer (GDE/GLB132.1P)
Sliding contact (P2)
Load
Voltage
Dual auxiliary switch contact rating
AC Rating
DC Rating
Switch Range
Switch A
Recommended range usage
Factory setting
Switch B
Recommended range usage
Factory setting
Switching hysteresis
Torque
GDE
GLB
Runtime for 90° opening or closing
GDE
GLB
Nominal angle of rotation
Maximum angular rotation
Shaft size: Minimum shaft length 3/4 inch (20 mm)
3/8 to 5/8 inch
8 -16 mm
Enclosure
GDE131.1N and GDE 131.1T
Material
Gear lubrication
OpenAir Non-Spring Return Rotary Electric Damper Actuator
24 Vac +20%, -15%
50/60 Hz
2.3 VA
Class 2 according to UL, CSA
Class III per EN60730
0 to 1000 ohm < 10 mA
< 1W
UL-Class 2 (SELV/PELV for CE)
< 24 Vac/dc
24 Vac/24 Vdc
4A resistive, 2A inductive
12 to 30 Vdc
DC 2A
0° to 90° with 5° intervals
0° to 45°
0° to 90° with 5° intervals
45° to 90°
85°
44 lb-in (5 Nm)
88 lb-in (10 Nm)
90 sec. at 60 Hz (108 sec. at 50 Hz)
125 sec. at 60 Hz (150 sec. at 50 Hz)
90°
95°
1/4 to 1/2 inch
6 - 12.7 mm
Figure 1. Acceptable Shaft Sizes.
NEMA Type 2
IP54 according to EN60529
NEMA1
Durable plastic
Silicone-free
24 Vac Floating Control
9/16 inch
15 mm
Siemens Building Technologies, Inc.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents