Non-spring return rotary 24 vac floating control electric damper actuator
Hide thumbs

Advertisement

Technical Instructions
Document No. 155-188P25
December 26, 2007
Start-Up/
Commissioning
Check the Auxiliary Switch A:
Check the Auxiliary Switch B:
Page 14
1.
Check that the wires are connected correctly.
2.
Connect wires 1 (red) and 6 (violet) to a Digital Multimeter (DMM) with the dial set at Vac.
Apply a control signal (24 Vac) to wires 1 and 6 to verify that the operating voltage is within
range.
3.
Connect wires 1 (red) and 7 (orange) to a DMM with the dial set at Vac. Apply a control
signal (24 Vac) to wires 1 and 7 to verify that the operating voltage is within range.
Check Operation:
1.
Connect wire 1 (red) to the actuator.
2.
Apply a control signal (24 Vac) to wires 1 (red) and 6 (violet).
3.
Allow the actuator shaft coupling to rotate from 0° to 90°.
4.
Stop applying a control signal to wires 1 (red) and 6 (violet).
5.
Apply a control signal (24 Vac) to wires 1 (red) and 7 (orange).
6.
Allow the actuator shaft coupling to rotate from 90° to 0°.
Check Feedback:
1.
Set the DMM dial to ohms.
2.
Connect wires P1 and P2 to the DMM. The DMM should indicate a resistive value.
3.
Apply a control signal (24 Vac) to wires 1 (red) and 6 (violet).
The reading of the DMM should increase.
4.
Connect wires P2 and P3 to the DMM. The DMM should indicate a resistive value.
5.
Apply a control signal (24 Vac) to wires 1 (red) and 7 (orange).
The reading of the DMM should increase.
1.
Set the DMM dial to ohms (resistance) or continuity check.
2.
Connect wires S1 and S3 to the DMM.
The DMM should indicate an open circuit or no resistance.
3.
Apply a control signal (24 Vac) to wires 1 (red) and 6 (violet).
The DMM should indicate contact closure as the actuator shaft coupling reaches the setting of
switch A.
4.
Stop applying a control signal to wires 1 (red) and 6 (violet).
5.
Connect wires S1 and S2 to the DMM.
The DMM should indicate an open circuit or no resistance.
6.
Apply a control signal (24 Vac) to wires 1 (red) and 7 (orange). The DMM should indicate contact
closure as the actuator shaft coupling reaches the setting of switch A.
1.
Set the DMM dial to ohms (resistance) or continuity check.
2.
Connect wires S4 and S6 to the DMM.
The DMM should indicate an open circuit or no resistance.
3.
Apply a control signal (24 Vac) to wires 1 (red) and 6 (violet). The DMM should indicate contact
closure as the actuator shaft coupling reaches the setting of switch B.
4.
Stop applying a control signal to wires 1 (red) and 6 (violet).
5.
Connect wires S4 and S5 to the DMM. The DMM should indicate an open circuit or no resistance.
6.
Apply a control signal (24 Vac) to wires 1 (red) and 7 (orange). The DMM should indicate contact
closure as the actuator shaft coupling reaches the setting of switch B.
OpenAir Non-Spring Return Rotary Electric Damper Actuator
Siemens Building Technologies, Inc.
24 Vac Floating Control