Below table shows all network variables on LIU005Z.
Index
nviRequest
0
nvoStatus
1
nciLocation
2
nciPwUpOutTm
3
nciRcvHrtBt
4
nciSndHrtBt
5
nciMinOutTm
6
nciMaxSpeed
7
nciMinSpeed
8
nciNmlSpeed
9
nciNmlFreq
10
nciRampUpTm
11
nciRampDownTm
12
nciDrvSpeedScale
13
nviDrvSpeedStpt
14
nviDrvSpeedScale
15
nviInvSetFreq
16
nviEmergOverride
17
nviDrvReset
18
nvoDrvSpeed
19
nvoDrvCurnt
20
nvoDrvVolt
21
nvoDrvPwr
22
nvoDrvRunHours
23
nvoInvOutFreq
24
nvoDrvSpeedOtpt
25
nviEmergStatus
26
nvoDrvAlarm
27
nvoTypeVer
28
29
nviInvP
nvoInvP
30
variable name
SNVT_obj_request
SNVT_obj_status
SNVT_str_asc
SNVT_time_sec
SNVT_time_sec
SNVT_time_sec
SNVT_time_sec
SNVT_lev_percent
SNVT_lev_percent
SNVT_rpm
SNVT_freq_hz
SNVT_time_sec
SNVT_time_sec
SNVT_lev_percent
SNVT_switch
SNVT_lev_percent
SNVT_freq_hz
SNVT_hvac_emerg
SNVT_state
SNVT_lev_percent
SNVT_amp
SNVT_volt
SNVT_power_kilo
SNVT_time_hour
SNVT_freq_hz
SNVT_switch
SNVT_hvac_emerg
SNVT_switch
SNVT_str_asc
specific
specific
SNVT type
Unit
--------
--------
Ascii
0.1s
0.1s
0.1s
0.1s
0.005%
0.005%
1min
0.1Hz
0.1s
0.1s
0.005%
0.5%,1
0.005%
0.1Hz
binary
boolean
0.005%
0.1A
0.1V
0.1kW
1h
0.1Hz
0.5%,1
binary
0.5%,1
Ascii
--------
--------
- 10 -
Default value
--------
--------
Null
0.0s
0.0s
0.0s
0.5s
100.000%
0.000%
-1
-1
1800min
60.0Hz
10.0s
10.0s
100.000%
{0.0%, -1}
nciDrvSpeedScale
3276.7Hz (Invalid)
EMERG_NORMAL
--------
--------
--------
--------
--------
--------
--------
--------
--------
--------