DWR SERIES SECTIONAL WALL MOUNT RACK LISTED THANK YOU Thank you for purchasing the DWR Series Sectional Wall Rack. Please read these instructions thoroughly before installing / assembling this product. PRODUCT FEATURES - Tool-Free Quick-Mount system allows easy, one person mounting of center...
A LICENSED PROFESSIONAL ENGINEER MUST APPROVE THE TYPE OF FASTENERS FOR THE WALL WHERE THE RACK WILL BE MOUNTED. BRACED ACCORDING TO SPECIFICATIONS SET FORTH BY LICENSED ARCHITECTS AND ENGINEERS, THE MIDDLE ATLANTIC PRODUCTS RACK/ENCLOSURE YOU PURCHASED IS CAPABLE OF SUSTAINING A PHENOMENAL LATERAL LOAD OF HIGH IMPORTANCE EQUIPMENT WITH THE FRONT RAILS FILLED TO A MAXIMUM CAPACITY OF 140 LBS.
INSTALLATION 1) Separate backpan from center section and determine hinge side. NOTE: DWR center section can be opened from left-to-right or vice versa depending on how backpan is installed. THE BACKPAN MUST BE INSTALLED PLUMB AND LEVEL FOR PROPER OPERATION. NOTE: Ensure the wall to which the backpan will be mounted, consists of two (2) 3/4"...
Page 4
INSTALLATION (CONTINUED) 4) Remove security clips located at top and bottom of unit. (FIGURE C) PIVOT PIN 5) Remove pivot pins located at the top and bottom of backpan. (FIGURE D) SECURITY CLIP FIGURE C 6) Lift the center section and place the bottom glide strip on the edge of the backpan.
GROUNDING AND BONDING Protective Earth Terminals (PET) are located in backpan of the wall rack. These terminals are marked with the symbol Wall rack parts, center section and door, contain or are provided with bonding points for connection to the backpan / PET. Protective earth and bonding connections shall be in accordance with Article 250 of the National Electric Code.
GROUNDING AND BONDING (Continued) 1) Attach backpan bonding wire from 1/4”-20 backpan protective earth terminal (PET) to nearest center section bonding stud (10-32) using hardware provided. (FIGURE G) NOTE: The main protective earth ground needs to be the first terminal placed on the PET and this terminal needs to be secured on its own with a nut.
DECORATOR-STYLE LASER KNOCKOUT The face of the top and bottom of the DWR wall rack has a knockout for the mounting of the RPS Series remote power switch from Middle Atlantic Products or any low voltage decorator-style device. DECORATOR-STYLE LKO...
POWER STRIP INSTALLATION Middle Atlantic Products power strips (PD-815SC, PD-815SC-NS, PD-2415SC,PD-2415SC-NS and PD-2420SC-NS only) can be mounted inside the center section trim with the included hardware. Simplifies cable management with no additional accessories required.
Page 9
VERTICAL POWER STRIP INSTALLATION NOTE: Requires Middle Atlantic Products part # PB-DWR (Sold Seperately). 1) Install PB-DWR power bracket (two provided) to Z bracket. Z BRACKET BACKPAN SECTION SLIDE NUT PHILLIPS HEAD SCREW 2) Quick clip (two Provided) for corded POWER STRIP model strips.
WARRANTY Middle Atlantic Products (the "Company") warrants the DWR Series Sectional Wall Mount Rack to be free from defects in material or workmanship under normal use and conditions for the lifetime of the product. The Company's entire liability to the purchaser, and the purchaser's (or any other party's) sole and...