3 Transport and Mounting
3.2

Storage

For storage of the MV Power Station note the following points:
• Do not place the MV Power Station on an unstable, uneven surface.
• Once the MV Power Station has been set down on the surface, do not attempt to adjust its position by pulling or
pushing.
• Prior to storage, ensure that the doors of the MV Power Station are tightly closed.
3.3

Requirements and Ambient Conditions

☐ The maximum permissible gradient of the access road is 8%.
☐ During unloading, a distance of at least 2 m to neighboring obstacles must be observed.
☐ The access roads and the unloading site must be designed to accommodate the length, width, height, total weight
and curve radius of the truck.
☐ Transport must be carried out by truck with air-sprung chassis.
☐ The unloading site for the crane and truck must be firm, dry and horizontal.
3.4

Unloading

The MV Power Station is unloaded by a crane. To unload the MV Power Station, the crane requires a swivel radius of
at least 6 m. To facilitate unloading, we recommend maintaining a distance of at least 2 m to neighboring obstacles
such as fences or trees.
Depending on the on-site conditions, further measures may be necessary (for example, when installation is to take
place near overhead lines). The conditions at the unloading site must have been thoroughly checked before transport.
Figure 6: Swivel radius for unloading the MV Power Station