Siemens SIMATIC CP 440 Manual page 28

Installation and parameter assignment
Table of Contents

Advertisement

Basic Principles of Serial Data Transmission
Performance Limits with 3964(R)
Performance Limits of the 3964(R) Procedure:
Further processing of the send/receive data by the PLC program in the
communication partner is not guaranteed. You can only ensure this by using a
programmable acknowledgment mechanism.
The block check of the 3964(R) procedure (EXOR logic operation) cannot
detect missing zeros (as a whole character) because a zero in the EXOR logic
operation does not affect the result of the calculation.
Although the loss of an entire character (this character has to be a zero!) is
highly unlikely, it could possibly occur under very bad transmission conditions.
You can protect a transmission against such errors by sending the length of the
data message along with the data itself, and having the length checked at the
other end.
2-10
Point-to-point connection CP 440 Installation and Parameter Assignment
A5E00057742-02