3. Plug gas shut off assembly box (5 ft. power cord) into
115VAC 5-15 receptacle near the range.
GAS SHUT OFF
ASSEMBLY BOX
115VAC 15A
POWERED
RECEPTACLE
(BY OTHERS)
4. There will be two (2) 6 ft. plug and play cables
coiled up in the hood. Run these through a two inch
knockout in the control j-box down to the gas shut off
assembly, connecting them per the diagram shown:
6 FT. CABLES FROM HOOD
(ATTACHED TO HOOD)
9 PIN
PLUG AND PLAY
CABLE
TOP VIEW
GAS SHUT OFF ASSEMBLY BOX
MOUNTED BEHIND RANGE
(FRONT VIEW)
TOP VIEW
FUEL ACTIVATION
CONTACT RATING
12 VAC - 5 AMP
AUXILIARY INTERFACE
CONTACT RATING
115 VAC - 5 AMP
12
Fire Ready Hood
RANGE (BY OTHERS)
5 FT. CORD
4 PIN
PLUG AND PLAY
CABLE
RIGHT SIDE
VIEW
RIGHT SIDE
VIEW
Electric (if applicable)
1. Plug range power cord into 250VAC receptacle on
electric shut off assembly box.
RANGE (BY OTHERS)
RANGE 250VAC
POWER CORD
ELECTRIC SHUT OFF
ASSEMBLY BOX
2. Plug gas shut off assembly box (2½ ft. 4-prong power
cord) into 250VAC 14-50 receptacle near the range.
ELECTRIC SHUT OFF
ASSEMBLY BOX
MAX 250VAC
MAX 50A 4-PRONG
POWERED
RECEPTACLE
(BY OTHERS)
3. There will be two (2) 6-ft. plug and play cables
coiled up in the hood. Run these through a two inch
knockout in the control j-box down to the electric
shut off assembly, connecting them per the diagram
shown.
6 FT. CABLES FROM HOOD
(ATTACHED TO HOOD)
4 PIN
PLUG AND PLAY
CABLE
LEFT SIDE
VIEW
RIGHT SIDE
VIEW
RANGE (BY OTHERS)
2½ FT. CORD
9 PIN
PLUG AND PLAY
CABLE
BACK VIEW
ELECTRIC SHUT OFF ASSEMBLY BOX
MOUNTED BEHIND RANGE
(TOP VIEW)