Guide Specifications (Cont'd)
QUANTECH
I. Protective Condensing Unit Panels (Factory or Field Mounted):
1. Louvered Panels (condenser coils only): Painted steel as per remainder of unit cabi-
net, over external condenser coil faces.
2. Wire Panels (full unit): Heavy gauge, welded wire-mesh, coated to resist corrosion,
to protect condenser coils from incidental damage and restrict unauthorized access
to internal components.
3. Louvered Panels (full unit): Painted steel as per remainder of unit cabinet, to protect
condenser coils from incidental damage,visually screen internal components, and
prevent unauthorized access to internal components.
4. Louvered/Wire Panels: Louvered steel panels on external condenser coil faces,
painted as per remainder of unit cabinet. Heavy gauge, welded wire-mesh, coated
to resist corrosion, around base of machine to restrict unauthorized access.
J. Service Isolation valves: Service suction and discharge (ball type) isolation valves are
added to unit per system. This option also includes a system high pressure relief valve
in compliance with ASHRAE15. (Factory-mounted.)
K. Hot Gas By-Pass: Permits continuous, stable operation at capacities below the mini-
mum step of unloading to as low as 5% capacity (depending on both the unit & operat-
ing conditions) by introducing an artificial load. Hot gas by-pass is available installed
on one or both refrigerant circuit(s).
L. Microprocessor Membrane Keypad Graphics on in lieu of Standard English:
1. French language.
2. German language.
3. Spanish language.
4. Italian language.
M. Chicago Code Relief Valves to meet Chicago Code requirements.
N. Building Automation System (EMS) Reset Interface: Condensing Unit to accept 4 to
20mA, 0 to 10 VDC, input to reset the discharge air temperature.
O. Sound Reduction (Factory Mounted):
1. Low speed, reduced noise fans
2. Compressor Acoustic Sound Blankets
P. Vibration Isolation (Field Mounted):
1. Neoprene Pad Isolators.
2. 1 Inch Deflection Spring Isolators: Level adjustable, spring and cage type isolators
for mounting under the unit base rails.
3. 2 Inch Deflection Seismic Isolators: Level adjustable, restrained mounts in rugged
welded steel housing with vertical and horizontal limit stops. Housings shall be de-
signed to withstand a minimum 1.0g accelerated force in all directions to 2 inches.
FORM QCC3-EG1 (517)
57