Single compressor 60 hz 120 tons to 200 tons (156 pages)
Summary of Contents for Quantech QCC3
Page 1
FORM QCC3-EG1 (517) MODEL QCC3 AIR-COOLED SCROLL COMPRESSOR CONDENSING UNITS STYLE A 80 – 160 TON 281 – 562 kW 60 Hz R-410A...
Page 2
FORM QCC3-EG1 (517) Nomenclature 145C DESIGN SERIES TYPE START X = ACROSS THE LINE VOLTAGE CODE: 17 = 200-3-60 28 = 230-3-60 40 = 380-3-60 46 = 460-3-60 58 = 575-3-60 Z = STANDARD EFFICIENCY Y = HIGH EFFICIENCY NOMINAL CAPACITY...
FORM QCC3-EG1 (517) Table Of Contents INTRODUCTION ..............................5 CONTROL CENTER ..............................6 ACCESSORIES AND OPTIONS ........................... 10 SELECTION DATA ..............................13 RATINGS ................................18 PART LOAD RATINGS ............................24 PHYSICAL DATA ..............................25 DIMENSION DRAWINGS ............................26 ISOLATORS ................................29 ELECTRICAL DATA ..............................
Page 4
FORM QCC3-EG1 (517) THIS PAGE INTENTIONALLY LEFT BLANK. QUANTECH...
FORM QCC3-EG1 (517) Introduction GENERAL The 80-160 Ton (273 - 560 kW) QCC3 Condensing Unit Models are shipped complete from the factory ready for field installation. The unit is pressure-tested, evacuated and given a nitrogen holding charge and includes an initial oil charge (R-410A refrigerant supplied by others). After assembly, a operational test is performed to assure that each control device operates correctly.
FORM QCC3-EG1 (517) Control Center All controls are contained in a NEMA 3R/12 cabinet with hinged outer door and include: Liquid Crystal Display with light emitting diode (LED) backlight ing suitable for outdoor viewing: • Two display lines • Twenty characters per line...
Page 7
• Suction pressure cutout setting • Each system suction pressure • System discharge pressure • Discharge Air Temperature Reset via a Quantech ISN DDC or Building Automation System (by oth ers) via: • - a pulse width modulated (PWM) input as standard • - a 4-20 milliamp or 0 -10 VDC input, or contact closure with the optional B.A.S.
Page 8
FORM QCC3-EG1 (517) Control Center (Cont'd) • Anti-recycle timer status for each system • Anti-coincident system start timer condition • Compressor run status • No cooling load condition • Day, date, and time • Daily start/stop times • Holiday status • Automatic or manual system lead/lag control (Discharge Air Temperature control...
Page 9
FORM QCC3-EG1 (517) Control Center (Cont'd) POWER PANEL Each panel contains: • Compressor power terminals • Compressor motor starting contactors per l.E.C.* • Control power terminals to accept incoming for 115-1-60 control power • Fan contactors & overload current protection The power wiring is routed through liquid-tight conduit to the compressors and fans.
Enclosure Panels (Unit) – Tamperproof Enclosure Panels prevent unauthorized access to units. Enclosure Panels can provide an aesthetically pleasing alternative to expensive fencing. Additionally, for proper head pressure control, Quantech recommends the use of Condenser Louvered Panels for winter applications where wind gusts may exceed five mph (eight km/h).
Page 11
4-20 milliamp, 0-10VDC or contact closure input to reset the discharge air tem- perature from a Building Automation System. (The standard control panel can be directly connected to a Quantech Building Automated System via the standard on board RS485 communication port.) Language LCD And Keypad Display –...
Page 12
FORM QCC3-EG1 (517) Accessories and Options (Cont'd) POWER OPTIONS: Compressor Power Connections – Single-point terminal block connection(s) are pro- vided as standard. The following power connections are available as options. (See electri- cal data for specific voltage and options availability.) Single Point Non-Fused Disconnect Switch –...
FORM QCC3-EG1 (517) Selection Data The ratings shown on pages 18 through 24 are based on unit operation in a well designed and properly piped system. SELECTION RULES 1. Capabilities are based on Refrigerant R-410A. 2. Ratings may interpolated, but must not be extrapolated.
Page 14
050.40-ES2 or ASHRAE refrigeration handbook guidelines. All piping design and installa- tion is the responsibility of the user. QUANTECH ASSUMES NO WARRANTY RESPONSIBILITY FOR SYSTEM OPERATION OR FAILURES DUE TO IMPROPER PIPING OR PIPING DESIGN. Filter driers and sight glasses are shipped loose for field installation on each refrigerant circuit.
Page 15
FORM QCC3-EG1 (517) Selection Data (Cont'd) REFRIGERANT LINE SIZING Refrigerant piping systems must be designed to provide practical line sizes without exces- sive pressure drops, prevent compressor oil from being “trapped” in the refrigerant piping, and ensure proper flow of liquid refrigerant to the thermal expansion valve. Consider- ations should be give to: 1.
Page 16
FORM QCC3-EG1 (517) Selection Data (Cont'd) OIL TRAPS All horizontal suction lines should be pitched at least 1/4” per foot (2 cm/m) in the direction of the refrigerant flow to aid in the return of oil to the compressor. All suction lines with a vertical rise exceeding 3 feet (.91 meters) should have a “P”...
Page 17
FORM QCC3-EG1 (517) Selection Data (Cont'd) TABLE 4 - REFRIGERANT LINE CONNECTIONS REFRIGERANT LINE SUCTION LINE LIQUID LINE MODEL VELOCITY CONNECTION SYSTEM NOMINAL COPPER COPPER @ NOMINAL TONS NUMBER TONS TYPE L TYPE L NUMBER CAPACITY QCC3 SUCTION LIQUID INCHES OD...
FORM QCC3-EG1 (517) Physical Data MODEL NUMBER QCC3 REFRIGERANT R-410A STANDARD EFFICIENCY UNITS 080CZE 085CZE 090CZE 100CYE 110CYE 130CZE 145CZE 160CZE GENERAL UNIT DATA Length 116.1 116.1 116.1 142.7 142.7 142.7 187.7 187.7 Width 88.0 88.0 88.0 88.0 88.0 88.0 88.0...
FORM QCC3-EG1 (517) Isolators EQUIPMENT BASE (BY OTHERS) POSITIONING LD18443 MOUNT DIMENSION DATA (INCHES) TYPE CP-1 7-3/4 6-1/2 4-3/4 5-5/8 CP-2 10-1/2 9-1/4 7-3/4 9/16 RATED CAPACITY (FOR UNITS WITH ALL LOAD POINTS MODEL NUMBER COLOR CODE LESS THAN 1785 LBS (810 KG) (LBS.)
Page 30
FORM QCC3-EG1 (517) Islators (Cont'd) RD-STYLE ISOLATORS MOLDED DURULENE MOLDED DURULENE Ø = AD Thru Typ 2 Places R = 0.280 Slot Typ 2 Places LD17304 MOUNT DIMENSION DATA (INCHES) TYPE 5/16-18 UNC RD1-WR 3.13 1.75 1.25 2.38 0.34 0.19 1.25...
Page 31
FORM QCC3-EG1 (517) Isolators (Cont'd) Y2RS 1-1/8” 5/8” 2-3/4” 2-3/4” 3/8” GAP 3/4” TYP. (4) 3/4” 7/8” STOP & 8-3/8” OPER. HEIGHT LD18442 WEIGHT RANGE WEIGHT RANGE VMC PART NUMBER VMC ISOL. COLOR (LBS) (KGS) Y2RSI-2D-460 GREEN Up thru 391...
FORM QCC3-EG1 (517) Electrical Data MINIMUM MIN DUAL MAX DUAL MIN N/F QCC3 VOLT CIRCUIT ELEMENT FUSE ELEMENT FUSE DISC SW AMPS & MIN CB & MAX CB 080CZE 085CZE 090CZE 100CYE 110CYE 130CZE 145CZE 160CZE QUANTECH...
FORM QCC3-EG1 (517) Electrical Notes NOTES: 1. Minimum Circuit Ampacity (MCA) is based on 125% of the rated load amps for the largest motor plus 100% of the rated load amps for all other loads included in the circuit, per N.E.C. Article 430-24. If the optional Factory Mounted Control Transformer is provided, add the following MCA values to the electrical tables for the system providing power to the transformer: -17, add 2.5 amps;...
Page 39
FORM QCC3-EG1 (517) THIS PAGE INTENTIONALLY LEFT BLANK. QUANTECH...
Page 48
FORM QCC3-EG1 (517) Electrical Drawings (Cont'd) o i t o i t - ADIS DISPLAY BOARD MANUAL MOTOR STARTER COMPRESSOR -QMMSC -QSD SWITCH DISCONNECT - BAMB AMBIENT - BDP DISCHARGE PRESSURE RESISTOR - BECT ENTERING CHILLED TEMPERATURE - BLCT LEAVING CHILLED TEMPERATURE...
Page 49
FORM QCC3-EG1 (517) Electrical Drawings (Cont'd) This drawing is based on IEC symbols. Field wiring to be in accordance with the relevant electrical code as well as all other applicable codes and specifications All sources of supply shown on this diagram to be taken from one main isolator, not shown or supplied by the chiller manufacturer .
Application Data UNIT LOCATION The QCC3 Condensing Units are designed for outdoor installation. When selecting a site for installation, be guided by the following conditions: 1. For outdoor locations of the unit, select a place having an adequate supply of fresh air for the condenser.
Page 51
FORM QCC3-EG1 (517) Application Data (Cont'd) Mounting holes (11/16” diameter) are provided in the steel channel for bolting the unit to its foundation. See Dimension Drawings on page 26. For ground level installations, precautions should be taken to protect the unit from tam- pering by or injury to unau thorized persons.
FORM QCC3-EG1 (517) Guide Specifications PART 1 – GENERAL 1.01 SCOPE A. The requirements of the General Conditions, Supplementary Conditions, Division 1, and Drawings apply to all Work herein. B. Provide Microprocessor controlled, multiple-scroll compressor, air-cooled, condensing units of the scheduled capacities as shown and indicated on the Drawings, including but not limited to: 1.
Page 53
FORM QCC3-EG1 (517) Guide Specifications (Cont'd) PART 2 - PRODUCTS 2.01 CONDENSING UNITS MATERIALS AND COMPONENTS A. General: Install and commission, as shown on the schedules and plans, factory as- sembled, charged, and tested air cooled scroll compressor condensing unit as speci- fied herein. Condensing Unit shall be designed, selected, and constructed using a...
Page 54
FORM QCC3-EG1 (517) Guide Specifications (Cont'd) 2.04 HEAT EXCHANGERS A. Air Cooled Condenser: 1. Coils: Internally enhanced, seamless copper tubes, mechanically expanded into aluminum alloy fins with full height collars. Subcooling coil an integral part of con- denser. Design working pressure shall be 650 psig (45 barg). 2. Fans: Shall be dynamically and statically balanced, direct drive, corrosion resistant...
Page 55
B. Exposed compressor, control and fan motor power wiring shall be routed through liquid tight conduit. 2.07 ACCESSORIES AND OPTIONS Some accessories and options supercede standard product features. Your Quantech Sales Representative will be pleased to provide assistance. A. Microprocessor controlled, Factory installed Across-the-Line type compressor motor starters as standard.
Page 56
FORM QCC3-EG1 (517) Guide Specifications (Cont'd) C. Power Supply Connections: 1. Single Point Power Supply: Single point Terminal Block for field connection and in- terconnecting wiring to the compressors. Separate external protection must be sup- plied, by others, in the incoming power wiring, which must comply with the National Electric Code and/or local codes.
Page 57
FORM QCC3-EG1 (517) Guide Specifications (Cont'd) I. Protective Condensing Unit Panels (Factory or Field Mounted): 1. Louvered Panels (condenser coils only): Painted steel as per remainder of unit cabi- net, over external condenser coil faces. 2. Wire Panels (full unit): Heavy gauge, welded wire-mesh, coated to resist corrosion, to protect condenser coils from incidental damage and restrict unauthorized access to internal components.
Page 58
FORM QCC3-EG1 (517) Guide Specifications (Cont'd) PART 3 - EXECUTION 3.01 INSTALLATION A. General: Rig and Install in full accordance with Manufacturers requirements, Project drawings, and Contract documents. B. Location: Locate condensing unit as indicated on drawings, including cleaning and service maintenance clearance per Manufacturer instructions.