Air-cooled scroll compressor condensing units style a 80 – 160 ton 281 – 562 kw 60 hz r-410a (60 pages)
Summary of Contents for Quantech QWC4
Page 1
WATER-COOLED SCREW LIQUID CHILLERS INSTALLATION, OPERATION, MAINTENANCE New Release Form QWC4-NM1 (221) 035-28391-000 MODEL QWC4 SINGLE COMPRESSOR 60 HZ 120 TONS TO 200 TONS R-134a Issue Date: February 28, 2021...
Page 2
All wiring must be in accordance with Quantech’ published specifications and must be performed only by a qualified electrician. Quantech will NOT be responsible for damage/problems resulting from improper con- nections to the controls or application of improper control signals.
Page 3
Exchange website at https://docs.johnsoncontrols.com/ chillers/. ASSOCIATED LITERATURE MANUAL DESCRIPTION FORM NUMBER QWC4 Chiller Installation Checklist QWC4-CL1 QWC4 Chiller Start-up Checklist and Request for Authorized Start-up Technician QWC4-CL3 QWC4 Renewal Parts QWC4-RP1 Limited Warranty QTC-NM2 QUANTECH...
Page 6
FORM QWC4-NM1 (221) ISSUE DATE: 02/28/2021 TABLE OF CONTENTS (CONT'D) Unit Piping ..............................57 Electrical Connection ............................57 Power Wiring ..............................57 Power Supply Wiring ............................57 115 VAC Control Supply Transformer ......................57 Control Wiring ..............................57 System Inputs ..............................58 Analog Inputs ..............................
Page 7
FORM QWC4-NM1 (221) ISSUE DATE: 02/28/2021 TABLE OF CONTENTS (CONT'D) SECTION 8 - TROUBLESHOOTING .........................147 Abnormal Operation, Analysis and Correction ..................... 147 Troubleshooting the Compressor and Oil Separation System ..............147 SECTION 9 - DECOMMISSIONING, DISMANTLING, AND DISPOSAL ............153...
Page 8
LIST OF FIGURES FIGURE 1 - Emergency Shutdown Handle ......................13 FIGURE 2 - QWC4 Chiller Major Components (Front View) ..................16 FIGURE 3 - QWC4 Chiller Major Components (Rear View) ...................17 FIGURE 4 - Basic System Control and VSD System Architecture .................18 FIGURE 5 - Control Center User Interface ......................20...
Page 9
FIGURE 58 - Manual Override and Print Key .......................122 FIGURE 59 - Printer Cable Connection from QWC4 Chiller to a Computer ............122 FIGURE 60 - Printer Cable Connection from QWC4 Chiller to a Serial Printer ............ 123 FIGURE 61 - Sample Printout ..........................125 FIGURE 62 - System Switches and Service Keys ....................127...
INTRODUCTION labor or extended warranty has been purchased as part Quantech QWC4 chillers are manufactured to the high- of the contract. est design and construction standards to ensure high performance, reliability, and adaptability to all types of The warranty is limited to parts only replacement and air conditioning installations.
FORM QWC4-NM1 (221) SECTION 1 - GENERAL CHILLER INFORMATION AND SAFETY ISSUE DATE: 02/28/2021 • GB/T 18430.1 - Water Chilling (Heat Pump) Pack- • Personal safety, the safety of other personnel, and ages Using The Vapor Compression Cycle - Part the equipment.
FORM QWC4-NM1 (221) SECTION 1 - GENERAL CHILLER INFORMATION AND SAFETY ISSUE DATE: 02/28/2021 Pressure Systems The unit contains refrigerant vapor and liquid under pres- sure, release of which can be a danger and cause injury. The user should make sure that care is taken during in- stallation, operation, and maintenance to avoid damage to the pressure system.
Page 14
FORM QWC4-NM1 (221) ISSUE DATE: 02/28/2021 THIS PAGE IS INTENTIONALLY LEFT BLANK. QUANTECH...
Quantech QWC4 chillers are designed for water or gly- COMPONENTS col cooling. All units are designed to be located in an The QWC4 chiller, as shown in Figure 2 on page 16 equipment room unless the unit was ordered specially and Figure 3 on page 17, consists of: for outside applications.
The QWC4 compressor is one of evaporator and condenser to ensure each circuit func- the most efficient and reliable screw compressors in tions correctly.
FORM QWC4-NM1 (221) SECTION 2 - PRODUCT DESCRIPTION ISSUE DATE: 02/28/2021 MICROCOMPUTER CONTROL CENTER The microcomputer control center, shown in Figure 5 on page 20, provides automatic control of chiller operation including compressor start/stop and load/un- load anti-recycle timers, condenser and chilled water (CHW) pumps, unit alarm contacts and run signal con- tacts.
Page 21
FORM QWC4-NM1 (221) SECTION 2 - PRODUCT DESCRIPTION ISSUE DATE: 02/28/2021 Double Thick Insulation 1 1/2 in. (38 mm) insulation servicing. Circuit breaker is sized to provide motor is available on the evaporator as a factory-installed op- branch, short circuit and ground fault protection for the tion.
The Head Pressure Control function provides an output QWC4 Chillers are capable of operation with- control signal that will respond to a programmed mini- in a wide range of condenser water tempera- mum chiller differential pressure.
Observe the following precautions: all units are tested and inspected before leaving the fac- • Notify the nearest Quantech office in ample time tory. The chiller may be ordered and shipped in any of for a Quantech representative to observe rigging...
Page 24
• All openings on the shells are closed and charged removed from the shells and skidded separately. with a 2 psig to 3 psig (115 kPa to 122 kPa) hold- Form 7 QWC4 chillers are shipped in the following as- ing charge of dry nitrogen. semblies: •...
• If the unit is stored longer than six months, follow ny's inspection. the requirements from Long-Term Storage Peri- odic Checklist and Logs for QWC4 Screw Chillers Quantech will not be responsible for any (Form 50.20-NM9). damage or loss of parts in shipment or at job site.
1129– 408–430 185–195 9515 4316 10421 4727 2606 1182 NOTE: Weights shown for base unit; selected options and tube count variations may add weights and/or refrigerant charge quantity to unit. Contact your nearest Quantech Sales Office for weight data. QUANTECH...
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 MOVING THE CHILLER FOR FORMS 1 AND 2 RIGGING Before moving the unit, make sure that the installation The complete standard unit (Forms 1 and 2) is shipped site is suitable for installing the unit and is easily ca- without skids.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 LOCATION TABLE 2 - SERVICE CLEARANCE REQUIRE- MENTS Locate the chiller in an indoor location with tempera- TUBE REMOVAL ADD MARINE ture ranges from 40°F to 110°F (4°C to 43°C) and ad-...
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 INSTALLING ELASTOMERIC VIBRATION ISOLATOR PADS Locate the elastomeric vibration isolator pads as shown The unit should be level within 0.25 in. (6 mm) from in Figure 9 on page 29 After placing the isolator one end to the other end, and from front to the rear.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 INSTALLING OPTIONAL SPRING ISOLATORS enough to level unit due to an uneven or sloping If ordered, four identical spring type isolator assemblies floor or foundation, add as many shims as neces- are furnished with the unit as shown in Figure 10 on sary (grouted, if necessary) under the isolator.
2. For wiring connections, refer to Field Connec- ances. See Figure 8 on page 28. tions and Control Wiring for QWC4 Chiller 2. Rig the evaporator and place in the final location (QWC4-PW2).
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 TABLE 4 - TORQUE SPECIFICATION UNIT QUANTECH TORQUE VALUE ITEM DESCRIPTION PART QUANTITY NUMBER FT-LBS. NUMBER END SHEETS (CON-EVAP ASSY) HCS5 0.625-11 X 2.500 GR 5 ZN...
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Installing the Evaporator Use the following instructions to install the evaporator 1. Attach the rigging chains from the overhead lift to as shown in Figure 11 on page 33.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Rigging and Installing the Condenser 1. Attach the rigging chains from the overhead lift to Use the following instructions to install the condenser the four lifting holes of the condenser (two at the as shown in Figure 12 on page 34.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Installing the Pads or Spring Isolators Use the following instructions to install the elastomeric 2. With an adequate lifting device lift the unit slight- pads or optional spring isolators as shown on page 36.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Installing the Heat Exchanger Piping Use the following instructions after the temporary ship- Connect the economizer heat exchanger liquid outlet pipes to the economizer on the evaporator, using the ping brackets supporting the heat exchanger piping has been removed as shown in Figure 14 on page 37.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Installing the Liquid Injection Piping Installing Oil Return Piping If equipped, install the optional liquid injection piping Install the oil return and piping between the filter drier...
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Installing Driveline Assembly Specific shim pads will be bolted to the Use the following instructions to install the driveline compressor supports to satisfy the align- (compressor/motor) assembly as shown in Figure 18 ment between the compressor and system on page 39.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Installing Oil Separator 2. Bolt the line to the flange on the oil separator and Use the following instructions to install the oil separator, to compressor discharge using the proper gaskets as shown in Figure 19 on page 41.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 With Isolation Ball Valve LD17759 See Table 4 on page 32 for Torque Specifications. FIGURE 19 - OIL SEPARATOR DISCHARGE PIPING ON SINGLE COMPRESSOR UNITS QUANTECH...
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Installing Variable Speed Drive (VSD) Use a spreader bar to ensure that the lift- Use the following instructions to install the VSD as ing chains do not bend the lifting tongs shown in Figure 22 on page 44.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Evaporator Condenser Evaporator Condenser Only be used for heat pump unit Only be used for standard air-conditioning ice storage unit and brine unit LD18956 FIGURE 25 - ALTERNATE PIPING FOR VSD...
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 PROCEDURES GASKET JOINTS Cleaning Assembling Gasket Joints Clean the parts visually contaminated with oil, grease, Use the following instructions to assemble the gasket or dirt with a generous spray of cleaner 7070. Wipe joints.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Torque Values Sealing is thus affected and maintained by the O-ring All threaded fasteners shall be torqued to the values compression which results from the clamping force shown in Table 13 on page 48 for the appropriate generated by tightening.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Back off locknut as far as possible. Make sure back-up 7. Inspect to ensure that O-ring is NOT pinched and washer is NOT loose and is pushed up as far as pos- the back-up washer seats flat on face of port.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 Assembly of O-ring Face Seal Fittings BRAZED JOINTS For personnel safety: Do not perform any The male end and female nut of face seal fittings have brazing or heat working unless the refrig- UN/UNF straight threads.
NPT connection can be ob- will likely show up as error in the sensor. tained from Quantech as an accessory for the unit. Al- As a precautionary measure, remove the ternatively, a differential pressure switch fitted across...
Consult a water treatment specialist to deter- loads, and at off-peak seasons of the year. QWC4 chill- mine if the proposed water composition will adversely ers can be operated with entering condensing water affect the evaporator materials of carbon steel and cop- temperature that is less than design conditions.
RATIO RANGE Air Conditioning 5–8 (min of 5) 5.5–8.8 (min of 3.3) The QWC4 chiller line has a maximum leaving Process 7–11 (min of 7) 7.7–12.3 (min of 4.4) water temperature of 60°F (15.6°C). Where process Install a tank or increase pipe sizes to provide suffi- applications require a chilled water temperature higher cient water volume.
American other design issues to evaluate with variable primary Society of Heating, Refrigeration and Air Conditioning flow systems. Consult the Quantech Sales Office for Engineers Standard 15 (ASHRAE 15) in North Amer- more information about successfully applying QWC4 ica, or PED code in Europe.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 When installing relief piping an ANSI flange or a piping union must be used to make a servicable piping connection. Horizontal Vertical Compressed Mis-aligned Offset When installing relief piping there must NOT be any piping strain.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 the panel end only, and run in water tight conduit. Run Remote Run Permissive shielded cable separately from mains cable to avoid A remote run permissive input is available and requires electrical noise pick-up.
Page 59
The function of the input is controlled by se- the unit, contact the Quantech Field Service Office to lecting the operating mode described in SECTION 6 schedule the start-up service.
Page 60
2. Unit assembled (if shipped dismantled) and re- NOTE: DO NOT cut to length or connect to frigerant piping installed ........drive without Quantech supervision ....3. Vibration isolator mounted so that the unit is 2. External control wiring completed according to level and isolators are equally deflected .....
Page 61
Year We understand that the services of the Quantech Authorized Representative will be furnished in accordance with the contract for a period of time of not more than _______ consecutive normal working hours, and we agree that a charge of _________ per diem plus travel expenses will be made to Quantech if services are required for longer than ________ consecutive normal hours or if repeated calls are required, through no fault of Quantech.
FORM QWC4-NM1 (221) SECTION 3 - HANDLING, STORAGE, INSTALLATION, AND REASSEMBLY ISSUE DATE: 02/28/2021 FIELD PROVIDED UNIT POWER SUPPLY SEE NOTE 1 VSD CONTROL PANEL STANDARD UNIT CONTROLS CONTROL TRANSFORMER NON-FUSED DISCONNECT SWITCH LINE REACTOR CIRCUIT BREAKER OPTION AVAILABLE INVERTER...
FORM QWC4-NM1 (221) SECTION 4 - TECHNICAL DATA ISSUE DATE: 02/28/2021 TABLE 24 - COMPLETE PIN NUMBER DESCRIPTION (CONT'D) DESCRIPTION OPTIONS OPTIONS DESCRIPTION Water Calcium Chloride Sodium Chloride CONDENSER FLUID Ethylene Glycol Propylene Glycol Special Quote 235 psig (1.62 MPa)
Page 71
FORM QWC4-NM1 (221) SECTION 4 - TECHNICAL DATA ISSUE DATE: 02/28/2021 TABLE 24 - COMPLETE PIN NUMBER DESCRIPTION (CONT'D) DESCRIPTION OPTIONS OPTIONS DESCRIPTION No SR Documents Monterrey base document Monterrey base & materials doc Sabadell base document Sabadell base & optional doc...
FORM QWC4-NM1 (221) SECTION 4 - TECHNICAL DATA ISSUE DATE: 02/28/2021 SINGLE COMPRESSOR UNIT DIMENSIONS TOP VIEW LD16476a SIDE VIEW FRONT VIEW LD16476b LD16476d FIGURE 39 - SINGLE COMPRESSOR UNIT DIMENSIONS QUANTECH...
Page 73
FORM QWC4-NM1 (221) SECTION 4 - TECHNICAL DATA ISSUE DATE: 02/28/2021 EVAPORATOR AND CONDENSER SHELL CODES IN (MM) DIMENSIONS SINGLE 145/151 DUAL 136/145 8ˊ (2438) 10ˊ (3048) 12ˊ (3658) 12' (3658) 14' (4268) 6ˊ-11/16" (1846) 6ˊ-11/16" (1846) 6ˊ-11/16" (1846) 6'-3/4" (1844) 6'-3/4"...
Make sure all checks are completed in the Start-up lower and middle of the upper sight glass of the oil Checklist (Form QWC4-CL3) on the next page. The separator. chiller is then ready to be placed into operation.
Page 78
........... shipped loose with the chiller. Refer to SEC- 4. Wiring is complete (power feed terminations in TION 7 - MAINTENANCE in the QWC4-NM1 for the VSD), and all sources of electrical supply to filling process............. the unit are taken from a single point of isolation 10.
Page 79
WARNING message appears, immediately con- This sensor must always be fully inserted in the tact QuanTech Product Technical Support to water outlet sensor well........request the password to reprogram the serial number, and any other important factory pro- 17.
Page 80
Refer to the PROGRAM 4. If the chilled and condenser liquid pumps are key in SECTION 6 - OPERATION in QWC4-NM1 for low and high limits, and default values. manually operated, start the pumps. The con- trol center will not allow the chiller to start un- 1.
Page 81
FORM QWC4-NM1 (221) SECTION 5 - COMMISSIONING ISSUE DATE: 02/28/2021 FORM QWC4-CL3 ISSUE DATE: 02/28/2021 9. When the compressor starts, press the relevant System Pressures key to verify that oil differen- tial pressure develops immediately. If oil pres- sure does not develop, the automatic controls will shut down the compressor.
Page 82
FORM QWC4-NM1 (221) ISSUE DATE: 02/28/2021 THIS PAGE IS INTENTIONALLY LEFT BLANK. QUANTECH...
FORM QWC4-NM1 (221) ISSUE DATE: 02/28/2021 SECTION 6 - OPERATION Keypad OPERATING CONTROLS DISPLAY An operator keypad allows complete control of the sys- tem from a central location. Access the following command keys on the left and right side of the keypad: •...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 Use the ▲,▼,◄, and ► keys to see the multiple dis- BASIC OPERATING SEQUENCE plays under a key. Once the ▲ ▼ keys are pressed and Start Sequence and Loading...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 • A low leaving chilled liquid temperature fault Remote Run Permissive Input occurs. The run permissive switches must have electrical con- • The VSD is requested to precharge for a run.
If there are questions about the following reset con- RESET analog input. A zero signal input (0%) trols, contact a Quantech BAS representative for de- equates to a 0°F (0°C) offset to the local setpoint. tails on BAS controls and capabilities.
Page 87
0°F (0°C) offset to the local setpoint. A full scale problems with chilled liquid temperature control. signal input (100%) equates to a negative offset A Quantech Factory Service Center should be to the local setpoint equal to the programmable contacted if a timer change is required.
15 minutes will create problems with chilled liquid tempera- • Remote Current Limit Analog Reset: Set the ture control. Contact a Quantech Factory Service CURRENT LIMIT setpoint via the REMOTE Center if a timer change is required.
STATUS message. When in this mode, no other STATUS messages can be seen. When power is first applied to the control panel, the following message displaying Quantech, EPROM ver- UNIT STATUS sion, date, and time will be displayed for two seconds,...
Page 90
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 rator pressure and overcome low differential pressure UNIT STATUS to maintain oil flow. CONDENSER LIQUID FLOW SWITCH SHUTDOWN The flow switch is open, which is preventing the unit Load or Unloading Limit Messages from running.
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 FAULT MESSAGES problems since it allows the service technician to view A number of possible fault messages may appear when operating parameters before a unit fault. Details on the the STATUS key is pressed. Whenever a fault message...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 JP6 Remote Sound Limit jumper position (Pins 1 to 2 3. Turn the Unit Switch OFF. (left) = 4 mA to 20 mA, Pins 2 to 3 (right) = 0 VDC to 4.
ENTER key. curred on March 3rd at 2:05pm, the user can import the Again, follow the Quantech Safety Directives to stop 20150303.csv file into Excel and look at the system the chiller, power off the unit and open the control cab- parameter details leading up to the 2:05pm event.
Contact INVALID SERIAL Quantech Product Technical Support immediately to get the password to enter the serial number NUMBER using the SERVICE key. Bypass this status message to view additional messages by pressing the STATUS key repeatedly.
Page 96
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 Unit safeties (faults), as shown in Table 32 on page First Fault Code 97, are: The first fault code will be set for the fault that initiated the system shutdown.
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 TABLE 31 - UNIT SAFETIES (FAULTS) MESSAGE DESCRIPTION Software-Initiated Fault - The voltage magnitude of each half of the DC bus shall remain within UNIT YYYYYYY +/- 100 VDC of the total DC bus voltage divided by two. If the magnitude exceeds the +/- 100 volt window the unit shall initiate a shutdown.
Page 98
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 TABLE 32 - UNIT SAFETIES FAULTS (CONT'D) MESSAGE DESCRIPTION The voltage magnitude of each half of the DC bus shall remain within +/- 100 VDC of the total UNIT YYYYYYY DC bus voltage divided by two.
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 TABLE 32 - UNIT SAFETIES FAULTS (CONT'D) MESSAGE DESCRIPTION Hardware-Initiated Fault - The various DC power supplies which power the logic board are monitored via hardware located on the logic board. If any power supply falls outside its allowable limits, the unit initiates a shutdown.
Page 100
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 TABLE 33 - SYSTEM SAFETIES FAULTS (CONT'D) MESSAGE DESCRIPTION Software-Initiated Fault - A system will fault and shut down with a ramped shutdown when the high discharge pressure rises above 333 psig (2300 kPa) for 0.5 seconds. The system will be allowed to restart when the discharge pressure falls to 293 psig (20.2 kPa).
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 TABLE 33 - SYSTEM SAFETIES FAULTS (CONT'D) MESSAGE DESCRIPTION Hardware-Initiated Fault - The mechanical High Pressure Cutout (HPCO) protects the system from experiencing dangerously high discharge pressure. A system will fault and shut down immediately when the mechanical high pressure cutout contacts open.
Page 102
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 TABLE 33 - SYSTEM SAFETIES FAULTS (CONT'D) MESSAGE DESCRIPTION This fault protects against excessive liquid refrigerant carryover from the economizer, in cases which may be a result of EEV, sensor or other problems. It also protects the system compressor from liquid refrigerant flooding back from the economizer feed line, in cases where the economizer valve fails to close.
Page 103
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 TABLE 33 - SYSTEM SAFETIES FAULTS (CONT'D) MESSAGE DESCRIPTION This fault is considered active when SMART FREEZE is turned on via the enable/disable setting, and the active LCHLT control setpoint is less than or equal to 38.0°F (3.3°C). SMART FREEZE can only be enabled or disabled while the chiller is stopped, and is only available in water applications.
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 UNIT DATA KEY UNIT DATA KEY FIGURE 49 - UNIT DATA KEY LD19539 The UNIT DATA key displays unit temperatures, and UNIT EVAP/COND PUMP RUN = ON OR OFF related data. Select the displays, which are listed se-...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 SYSTEM DATA KEY SYSTEM DATA KEY FIGURE 50 - SYSTEM DATA KEY LD19539 System Data Key Operation The SYSTEM DATA key gives access to SYSTEM operating parameters. The following list shows the data in the order in which they appear.
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 Display, if control is enabled. Sensor Displays Table 36 on page 106 lists all the sensors attached VI STEP SOLENOID 1 = ON OR OFF to the control board associated with SYSTEM DATA VI STEP SOLENOID 2 = ON OR OFF keys.
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 VSD DATA AND OPERATING HOURS/START COUNTER KEYS VSD DATA OPERATING HOURS/START COUNTER KEY LD19539 FIGURE 51 - VSD DATA AND OPERATING HOURS/START COUNTER KEYS The VSD DATA key provides multiple displays of VSD IGBT BASEPLATE TEMPS T1 = ### °F...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 HISTORY KEY HISTORY LD19539 FIGURE 52 - HISTORY KEY For all faults generated by the control To access the HISTORY FAULT or NORMAL SHUT- DOWN information, use the following steps:...
Page 109
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 If there are no ALL FAULTS for the current history, • OPTIONS on page 118 the following message will be displayed for the ALL • Display Language FAULTS screen. • Liquid Type, etc.
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 SETPOINTS KEY SETPOINTS KEY LD19539 FIGURE 53 - SETPOINTS KEY Press the SETPOINTS key to program: This message (above) will display the remote setpoint and control, which automatically updates. If there is •...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 PROGRAM KEY PROGRAM KEY LD19539 FIGURE 55 - PROGRAM KEY Press the PROGRAM key to modify the following nu- PROGRAM ◄DEF 103 LO 30 HI 103 meric operating parameters, which are displayed when...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 PROGRAM HPC DIRECTION PROGRAM ◄DEF 0.0% LO 0.0% HI 100.0% ◄► XXXXXXXXXXXXXXXXXXXXXXXXXXXX HPC SHUTDOWN POSITION = XX.X PROGRAM ◄DEF 0.0% LO 0.0% HI 100.0% HPC MINIMUM POSITION = XX.X TABLE 37 - PROGRAM LIMITS...
Page 114
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 Table 39 on page 116 - Setup Mode Programmable SETUP MODE ◄DEF 50.0 LO 50.0 HI 95.0 Values lists the values that can be programmed in this MIN START FREQ SETP = ##.# HZ...
Page 115
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 SETUP MODE ◄DEF 2.0 LO 0.1 HI 10.0 SETUP MODE VI STEP VALVE LVL CTRL INCREMENT 1 SETP = ##.# % ◄► ENABLED SETUP MODE ◄DEF 0.5 LO 0.1 HI 10.0 SETUP MODE ◄DEF 195.0...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 OPTIONS KEY OPTIONS KEY LD19539 FIGURE 56 - OPTIONS KEY The OPTIONS key displays unit configuration and the Remote Temperature Reset Input capability to modify it. To view the current settings, The display will only appear if the TEMP RESET op- press this key.
Page 119
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 Remote Current Limit Input Choose one LIMIT INPUT below, default is DIS- ABLED: OPTIONS REMOTE CURRENT LIMIT INPUT ◄ ► DISABLED OPTIONS REMOTE CURRENT LIMIT INPUT ◄ ► 0.0 TO 10.0 VOLTS DC...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 DATE/TIME AND SCHEDULE KEY DATE/TIME KEY SCHEDULE KEY LD19539 FIGURE 57 - DATE/TIME AND SCHEDULE KEY CLOCK FRI 13-APR-2012 10:15:33 AM CLOCK FRI APR-2012 10:15:33 AM DAY OF WEEK ◄ ►...
Page 121
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 To view the schedule without making a change, press change in memory. Press the SCHEDULE key a sec- the SCHEDULE key until the day appears. The ▲ key ond time to show the individual days: will scroll to the previous screen.
• All normal shutdowns (compressor cycling, chill- LD16479 er shutdown, etc.) FIGURE 59 - PRINTER CABLE CONNECTION • History (fault) data of a specific fault. History FROM QWC4 CHILLER TO A COMPUTER Buffer 1 will always be the most recent fault his- tory printout. QUANTECH...
PRINTER CONNECTIONS FIGURE 60 - PRINTER CABLE CONNECTION Connect the printers to the control center microboard FROM QWC4 CHILLER TO A SERIAL PRINTER as follows. Only one printer can be connected at a time. TABLE 39 - OKIDATA OKIPOS 441...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 Okidata OKIPOS 441 Printer TABLE 40 - PRINTOUT TYPES 1. With the printer power turned off, remove the two PRINTOUT TYPES screws, which hold the RS-232 Interface Module. Operating Data (Default) 2.
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 Operating Data Printout START COUNTER 1=XXXXX, 2=XXXXX SOFTWARE VERSION C.WCS.30.00 OPERATING DATA UNIT SERIAL NUMBER YYYY XXXZZZ 2:04:14 PM 9 MAR 12 VSD DATA SYS 1 COMPRESSOR RUNNING ACTUAL FREQUENCY XXX.X HZ...
Page 126
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 History Data Printout VSD SOFTWARE RUN SIGNAL History printouts provide stored data relating to all spe- EDUCTOR TEMPERATURE 68.8 DEGF cific system and chiller operating conditions at the time of the fault, regardless if a lockout occurred. Whenever...
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 SYSTEM SWITCHES AND SERVICE KEY SERVICE KEY SYSTEM SWITCHES KEY LD19539 FIGURE 62 - SYSTEM SWITCHES AND SERVICE KEYS Press the key to enter the switch selection into SYSTEM SWITCHES ON / OFF / RESET memory.
Feature 54. If there is no value to be sent Gateway as shown in Figure 63 on page 128. The to a particular page, a zero will be sent to the QWC4 first four are analog values and the last four are digi- Communications Data Map.
FORM QWC4-NM1 (221) SECTION 6 - OPERATION ISSUE DATE: 02/28/2021 TABLE 41 - REAL TIME NUMBER ERRORS ERROR DESCRIPTION NUMBER (##) ALL OK DATUM TYPE OK TEST FAILED ENGLISH TEXT TOO LONG FLOATING POINT EXCEPTION GET PACKET FAILED GET TYPE FAILED...
Page 130
FORM QWC4-NM1 (221) ISSUE DATE: 02/28/2021 THIS PAGE IS INTENTIONALLY LEFT BLANK. QUANTECH...
¹ This procedure must be performed at the specified time interval by an industry certified technician, who has been trained and qualified to work on this type of Quantech equipment. A record of this procedure being successfully carried out must be maintained on file by the equipment owner should proof of adequate maintenance be required at a later date for warranty validation purposes.
SECTION 7 - MAINTENANCE ISSUE DATE: 02/28/2021 DAILY OPERATING INSPECTIONS Oil Level The QWC4 chiller DOES NOT HAVE an oil pump. Routine Inspections System oil flow is dependent on the pressure differen- Avoid serious operating difficulties by conducting reg- tial between the condenser and evaporator. Therefore, ular inspections.
< 300 < 0.5 of time, refrigerant can condense in the oil separa- The QWC4 chiller compressors use rolling element tor. Unload and hold the chiller at a capacity that bearings (ball and roller bearings); no sleeve bear- allows the discharge superheat to increase above ings are used.
FORM QWC4-NM1 (221) SECTION 7 - MAINTENANCE ISSUE DATE: 02/28/2021 Adding Compressor Oil Add the new YORK oil into the oil separator with the 3. Open the oil charging valve and pump oil into the YORK oil charging pump (P/N 470-10654), and pro-...
OIL FILTER REPLACEMENT 7. Replace the oil filter element and the cover O- ring with new parts. Refer to Model QWC4 Re- Use the following instructions to replace the oil filter. newal Parts (Form QWC4-RP1) to get the new 1.
FORM QWC4-NM1 (221) SECTION 7 - MAINTENANCE ISSUE DATE: 02/28/2021 Replacing the Filter Drier If the eductor flow seems restricted by high eductor 6. Remove the filter drier from the eductor block and outlet temperatures or if the oil is replaced, replace the discard filter drier and Teflon seals (item 5).
Form 1 QWC4 chillers are charged with the correct Checking the Motor Windings amount of refrigerant. Under some operating condi- Make sure the motor power leads are marked and dis- tions, the chiller may appear to be overcharged or un- connect them from the output terminals in the VSD.
• Check refrigerant relief valve piping and evapora- tor and condenser tube rolled joints. PRESSURE CONNECTIONS All threaded pressure connections used on the QWC4 FIGURE 67 - MOTOR WINDINGS DIAGRAM chillers are SAE straight thread, O-ring face seal fit- tings or Primore Roto lock fittings.
FORM QWC4-NM1 (221) SECTION 7 - MAINTENANCE ISSUE DATE: 02/28/2021 2. To make sure that the concentration of refriger- 2. Wash off both tube heads and the ends of all tubes ant reached all parts of the system, slightly open with water.
FORM QWC4-NM1 (221) SECTION 7 - MAINTENANCE ISSUE DATE: 02/28/2021 EVACUATION AND DEHYDRATION OF UNIT See Table 45 on page 140 to see the relation between Make sure the power is removed from the dew point temperature and system pressure in inches of input side of the VSD at all times when mercury (vacuum).
FORM QWC4-NM1 (221) SECTION 7 - MAINTENANCE ISSUE DATE: 02/28/2021 Improve Dehydration gen into the system to bring it to atmospheric pressure Circulate hot water (not to exceed 125°F (52°C) and the indicator temperature will return to approxi- through the evaporator and condenser tubes to thor- mately ambient temperature.
Remove the rust or sludge from the tubes using a TUBES thorough brushing process. The condenser and evaporator tubes in a QWC4 chiller are made of copper with mild carbon steel waterboxes. 2. Scale – due to mineral deposits. These deposits,...
Page 143
3.14 x shell length (ft) x number of tubes/77 • An excessive quantity of oil in the evaporator. Contact a Quantech Field Service Office for the size Waterside Tube Cleaning Procedure and number of tubes. Two methods are used for waterside tube cleaning to Mechanical tube cleaning must always remove scale: chemical or mechanical.
For information covering the control center opera- tion, see SECTION 6 - OPERATION in this manual, 2. Remove the waterboxes from both ends of the and Field Connections and Control Wiring for QWC4 condenser with proper lifting equipment. Use cau- Chiller (Form QWC4-PW2).
Page 145
If a unit fails due to improper maintenance ant pump to verify the level in the fill tube. during the warranty period, Quantech will 6. Make sure the coolant level in the VSD cooling NOT be liable for costs incurred to return the system to satisfactory operation.
Page 146
FORM QWC4-NM1 (221) ISSUE DATE: 02/28/2021 THIS PAGE IS INTENTIONALLY LEFT BLANK. QUANTECH...
Page 147
TROUBLESHOOTING THE COMPRESSOR AND OIL SEPARATION SYSTEM Troubleshooting the compressor is limited to iden- tifying the probable cause. If a mechanical problem is suspected, contact the Quantech Field Service Office. DO NOT DISASSEMBLE THE COM- PRESSOR. QUANTECH...
FORM QWC4-NM1 (221) SECTION 8 - TROUBLESHOOTING ISSUE DATE: 02/28/2021 TABLE 45 - TROUBLESHOOTING GUIDE PROBLEM POSSIBLE CAUSE ACTION High voltage to the chiller is missing. Check 1FU, 2FU, 3FU, 4FU, 5FU, 14FU, Electric supply to the panel is missing.
Page 149
Replace compressor heater. Pressure Fluctuation Oil filter is dirty. Change oil filter. System Fault: Call Quantech Field Service Office to Oil Pressure Gradually Decreases Extreme bearing wear. evaluate compressor. Filter in oil return system dirty. Replace old oil filter with a new filter.
FORM QWC4-NM1 (221) SECTION 8 - TROUBLESHOOTING ISSUE DATE: 02/28/2021 TABLE 48 - PRESSURE TRANSDUCER EVAP PRESSURE ECONOMIZER PRESSURE DISCHARGE, CONDENSER, OIL PRESSURE (125 PSIG) (275 PSIG) (400 PSIG) PRESSURE VOLTAGE PRESSURE VOLTAGE PRESSURE VOLTAGE PRESSURE VOLTAGE PRESSURE VOLTAGE 3.12 0.66...
Page 152
FORM QWC4-NM1 (221) ISSUE DATE: 02/28/2021 THIS PAGE IS INTENTIONALLY LEFT BLANK. QUANTECH...
Page 153
FORM QWC4-NM1 (221) ISSUE DATE: 02/28/2021 SECTION 9 - DECOMMISSIONING, DISMANTLING, AND DISPOSAL Never release refrigerant to the atmo- 6. If glycol was used in the water system, or chemi- sphere when emptying the refrigerating cal additives are contained, dispose of the solu- circuits.
FORM QWC4-NM1 (221) ISSUE DATE: 02/28/2021 The following factors can be used to convert from English to the most common SI Metric values. TABLE 49 - SI METRIC CONVERSION MEASUREMENT MULTIPLY ENGLISH UNIT BY FACTOR TO OBTAIN METRIC UNIT Capacity Tons Refrigerant Effect (ton) 3.516...