Guide Specifications - Quantech QCC3 Manual

Air-cooled scroll compressor condensing units style a 80 – 160 ton 281 – 562 kw 60 hz r-410a
Table of Contents

Advertisement

FORM QCC3-EG1 (517)

Guide Specifications

PART 1 – GENERAL
1.01 SCOPE
A. The requirements of the General Conditions, Supplementary Conditions, Division 1,
and Drawings apply to all Work herein.
B. Provide Microprocessor controlled, multiple-scroll compressor, air-cooled, condensing
units of the scheduled capacities as shown and indicated on the Drawings, including
but not limited to:
1. Condensing Unit package
2. Electrical power and control connections
3. DX Central Station Air Handling connections
1.02 QUALITY ASSURANCE
A. Products shall be Designed, Tested, and installed in compliance with applicable sec-
tions of the following Standards and Codes:
1. ANSI/ASHRAE Standard 15 – Safety Code for Mechanical Refrigeration
2. ASHRAE 90.1 - Energy efficiency compliance.
3. ANSI/NFPA Standard 70 – National Electrical Code (N.E.C.).
4. Conform to Intertek Testing Services, formerly ETL, for construction of condensing
units and provide E.T.L./c E.T.L. Listing label.
5. Manufactured in facility registered to ISO 9002.
B. Factory Test: Condensing Unit shall be pressure tested, evacuated and given a nitro-
gen holding charge and an initial oil charge, and shall be factory operational run tested
to assure each control device operates properly.
C. Warranty: Manufacturer shall Warrant all equipment and material of its manufacture
against defects in workmanship and material for a period of one year from date of initial
start-up or eighteen (18) months from date of shipment, whichever occurs first.
1.03 DELIVERY AND HANDLING
A. Unit shall be delivered to job site fully assembled, and given nitrogen holding charge
and a full oil charge by the Manufacturer. (R-410A refrigerant supplied by others).
B. Unit shall be stored and handled per Manufacturer's instructions.
52