Segment 6 can be configured according to the possibilities indicated in Figure 21. Note that segment 7 and 8
cannot be configured.
-----------------------------------------------------------------------------
Segment 6 Function
-----------------------------------------------------------------------------
-----------------------------------------------------------------------------
Please Enter Number:
Functions description:
1. Battery Mode Shutdown: If this signal is activated and the UPS is on battery mode, the UPS output will be
disconnected.
2. Any Mode Shutdown: If this signal is activated, the UPS output will be disconnected.
3. Emergency Power Off: If this signal is activated, the UPS output will be disconnected and give the EPO
warning. The UPS cannot then be turned on by pressing the LCD buttons.
4. Remote On/Off: If this signal is activated (close Pin 8 and Pin1 when Segment 6 is configured to Normally
Open; or open Pin 8 and Pin1 when Segment 6 is configured to Normally Close) the UPS output will be
disconnected.
If Signal is not active (open Pin 8 & Pin1 when Segment 6 is configured to Normal Open; or close Pin 8 &
Pin1 when Segment 6 is configured to Normal Close) the UPS will turn on.
1.5.2.4 Function Segment Active Delay Time menu
The Function Segment Active Delay Time and current settings value can be configured as follows.
-----------------------------------------------------------------------------
Function Segment Active Delay Time
-----------------------------------------------------------------------------
-----------------------------------------------------------------------------
Please Enter Number:
The segments' default configuration is to execute "immediately".
Type 00 and Enter to configure the settings to "Immediately". Type 01 and Enter to configure a one second
delay.
-----------------------------------------------------------------------------
Segment 1 Active Delay Time
-----------------------------------------------------------------------------
Please Enter Delay Time 00~99,
Only Pressing <ENTER> Means Abort and Exit Current Setting
Please Enter Delay Time:
1. Battery Mode Shutdown
2. Any Mode Shutdown
3. Emergency Power Off
4. Remote On/Off
0. Exit
Figure 21: Input function select menu
1. Segment 1 Active Delay Time, Current Setting(Immediately)
2. Segment 2 Active Delay Time, Current Setting(Immediately)
3. Segment 3 Active Delay Time, Current Setting(Immediately)
4. Segment 4 Active Delay Time, Current Setting(Immediately)
5. Segment 5 Active Delay Time, Current Setting(Immediately)
6. Segment 6 Active Delay Time, Current Setting(Immediately)
0. Exit
Figure 22: Active delay time Segment select menu
Figure 23: Active delay time menu
4NWP100446R0001_OPM_ABB_AS400RelayCardPowerValue_EN140226
Modifications reserved
Page 14/15 ABB