Download Print this page
ABB ARS Series Instruction Leaflet
ABB ARS Series Instruction Leaflet

ABB ARS Series Instruction Leaflet

Auxiliary relay high speed

Advertisement

Quick Links

Effective: May 1999
Supersedes I.L. 41-759.2C, dated June 1985
( ) Denotes Change Since Previous Issue
CAUTION
!
Before putting protective relays into service,
remove all blocking which may have been
inserted for the purpose of securing the parts
during shipment. Make sure that all moving parts
operate freely. Inspect the contacts to see that
they are clean and can close properly. Operate
the relay to check the settings and electrical con-
nections.
1.0 APPLICATION
The ARS relay is a high speed auxiliary that has a 20
volt low energy level input and a multiple contact out-
put. It may be used as a tripping auxiliary for relays
such as the SP and SDG-1 or as an oscillograph
interface.
The driving device must be capable of providing an
input to the ARS of 6 milliamperes at a level of 15 to
20 volts.
2.0 CONSTRUCTION AND OPERATION
The type ARS relay is composed of 1 or 2 AR units
with series resistors, a printed circuit module, and
indicating contactor switches (ICS) when required,
mounted in a FT-11 or FT-22 case, depending upon
style.
AR Unit
The relay consists of four stationary contact screws,
All possible contingencies which may arise during installation, operation or maintenance, and all details and
variations of this equipment do not purport to be covered by these instructions. If further information is
desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the
local ABB Power T&D Company Inc. representative should be contacted.
Printed in U.S.A.
ABB Automation, Inc.
Substation Automation and Protection Division
Coral Springs, FL 33065
four leaf spring moving contacts, a moving armature
and card assembly, which operates the moving con-
tacts; a U shaped laminated core, a coil, a frame, a
molded insulation block and a series resistor.
The armature and card assembly slip over a hinge
pin which is inserted in the laminations. The moving
and stationary contacts are mounted on the molded
insulation block. The molded block and coil and lami-
nation assembly are mounted to the frame. All con-
tacts are fine silver.
When the coil and resistor are energized, the arma-
ture is attracted to the laminations. The card moves
with the armature thereby operating the moving con-
tacts. The tension of the moving contacts is the reset-
ting force.
High speed operation is obtained by the low inertia of
the moving parts, a sensitive electromagnet, and the
proper L/R ratio of the operating circuit.
Printed Circuit Module
The printed circuit module contains the proper num-
ber of transistors, protective zener diodes, capacitors,
resistors, and diodes for the buffered amplifier cir-
cuitry controlling each AR unit. With the rated supply
voltage to the relay, the proper signal voltage applied
to an input terminal will cause the related AR unit to
pickup. The AR unit will then energize the ICS (if
used), which will seal around the AR unit contacts.
The removal of the input voltage will cause the AR
unit to drop out.
Indicating Contactor Switch Unit (ICS)
The dc indicating contactor switch is a small clapper
Instruction Leaflet
Type ARS
Auxiliary Relay
High Speed
41-759.2D

Advertisement

loading

Summary of Contents for ABB ARS Series

  • Page 1 If further information is desired by purchaser regarding this particular installation, operation or maintenance of this equipment, the local ABB Power T&D Company Inc. representative should be contacted. Printed in U.S.A.
  • Page 2 I.L. 41-759.2D ARS Relay type device. A magnetic armature, to which leaf- AR Unit spring mounted contacts are attached, is attracted to All AR units are capable of being energized continu- the magnetic core upon energization of the switch. ously. All high speed relays will pick up at 80% of When the switch closes, the moving contacts bridge rated voltage or less;...
  • Page 3: Adjustments And Maintenance

    ARS Relay I.L. 41-759.2D Table 3: connections may be made directly to the terminals by Maximum Circuit Delay Time means of screws for steel panel mounting or to the terminal studs furnished with the relay for thick panel Delay mounting. The terminal studs may be easily removed Input Voltage Time in...
  • Page 4: Renewal Parts

    I.L. 41-759.2D ARS Relay 3. Armature gap turbed or are in error, or it becomes necessary to replace some part, use the following adjustment pro- The armature gap should be 0.009 inches mea- cedure. sured at the narrowest part of the armature gap. a.
  • Page 5 ARS Relay I.L. 41-759.2D Number Of Units Relay Circuit Board Style Internal Circuit Board Component Number Description Schematic Style Number Location FT-11 Case (Fig. 27) 718B820A09 48 Vdc; 2M contacts 719B963 (Fig. 1) 204C674G01 880A436 (Fig. 5) 718B820A10 125 Vdc; 2M contacts 719B963 (Fig.
  • Page 6 I.L. 41-759.2D ARS Relay *Sub 6 719B963 Figure 1. Relay Type ARS Single Input Buffer; 1 AR Unit with 2M Contacts; 2 ICS Units in FT-11 Case, 48 and 125 Vdc. *Sub 4 719B944 Figure 2. Relay Type ARS Single Input Buffer; 1 AR Unit with 2M Contacts; 2 ICS Units in FT-11 Case; 250 Vdc. * Denotes change since previous issue...
  • Page 7 ARS Relay I.L. 41-759.2D *Sub 6 719B945 Figure 3. Relay Type ARS Single Input Buffer; 1 AR Unit with 2M Contacts; 1 ICS Unit in FT-11 Case; 48 and 125 Vdc. *Sub 4 719B946 Figure 4. Relay Type ARS Single Input Buffer; 1 AR Unit with 2M Contacts; 1 ICS Unit in FT-11 Case; 250 Vdc. * Denotes change since previous issue...
  • Page 8 I.L. 41-759.2D ARS Relay *Sub 5 880A436 Figure 5. Component Location Single Input Buffer in Type FT-11 Case; 48 Vdc. *Sub 4 880A435 Figure 6. Component Location Single Input Buffer in FT-11 Case; 125 Vdc. * Denotes change since previous issue...
  • Page 9 ARS Relay I.L. 41-759.2D *Sub 4 880A433 Figure 7. Component Location Single Input Buffer in FT-11 Case; 250 Vdc. *Sub 4 719B951 Figure 8. Relay Type ARS 2 Buffered Input “OR”; 1 AR Unit 2M2B Contacts in FT-22 Case; 48 and 125 Vdc. * Denotes change since previous issue...
  • Page 10 I.L. 41-759.2D ARS Relay *Sub 5 719B952 Figure 9. Relay Type ARS 2 Buffered Input “OR”; 1 AR Unit 4M Contacts in FT-22 Case; 48 and 125 Vdc. *Sub 4 719B947 Figure 10. Relay Type ARS 2 Buffered Input “OR”; 1 AR Unit 2M2b Contacts; 2 ICS Units in FT-22 Case. * Denotes change since previous issue...
  • Page 11 ARS Relay I.L. 41-759.2D *Sub 5 719B948 Figure 11. Relay Type ARS 2 Buffered Input “OR”; 1 AR Unit 2M2B Contacts; 2 ICS Units in Ft-22 Case; 250 Vdc. *Sub 4 719B956 Figure 12. Relay Type ARS 2 Buffered Input “OR”; 1 AR Unit 4M Contacts; 2 ICS Units in Ft-22 Case; 48 and 125 Vdc. * Denotes change since previous issue...
  • Page 12 I.L. 41-759.2D ARS Relay *Sub 4 880A962 Figure 13. Component Location 2 Buffered Input “OR” in FT-22 Case; 48 Vdc. *Sub 4 880A434 Figure 14. Component Location 2 Buffered Input “OR” in Ft-22 Case; 125 Vdc. * Denotes change since previous issue...
  • Page 13 ARS Relay I.L. 41-759.2D *Sub 4 880A431 Figure 15. Component Location 2 Buffered Input “OR” in FT-22 Case; 250 Vdc. *Sub 4 719B953 Figure 16. Relay Type ARS 2 Single Buffered Inputs; 2 AR Units (All Make) Contacts in FT-22 Case; 48 and 125 Vdc. * Denotes change since previous issue...
  • Page 14 I.L. 41-759.2D ARS Relay *Sub 4 719B950 Figure 17. Relay Type ARS 2 Single Buffered Inputs; 2 AR Units 4M-2M2B Contacts in Ft-22 Case; 48 and 125 Vdc. *Sub 4 719B949 Figure 18. Relay Type ARS 2 Single Buffered Inputs; 2 AR Units 2M2B-2M2B Contacts in Ft-22 Case; 48 and 125 Vdc. * Denotes change since previous issue...
  • Page 15 ARS Relay I.L. 41-759.2D *Sub 4 719B954 Figure 19. Relay Type ARS 2 Single Buffered Inputs; 2 AR Units (All Make) Contacts; 2 ICS Units in FT-22 Case; 48 and 125 Vdc. *Sub 4 719B955 Figure 20. Relay Type ARS 2 Single Buffered Inputs;...
  • Page 16 I.L. 41-759.2D ARS Relay *Sub 4 719B957 Figure 21. Relay Type ARS 2 Single Buffered Inputs; 2 AR Units 2M2B-2M2B Contacts; 2 ICS Units in FT-22 Case; 125 Vdc. *Sub 4 719B958 Figure 22. Relay Type ARS 2 Buffered Input “OR”; 1 AR Unit 4M Contacts; 2 ICS Units in FT-22 Case; 250 Vdc. * Denotes change since previous issue...
  • Page 17 ARS Relay I.L. 41-759.2D *Sub 5 880A965 Figure 23. Component Location 2 Single Buffered Inputs in Type FT-22 Case; 28 Vdc. *Sub 4 880A964 Figure 24. Component Location 2 Single Buffered Inputs in Type FT-22 Case; 125 Vdc. * Denotes change since previous issue...
  • Page 18 I.L. 41-759.2D ARS Relay *Sub 4 880A963 Figure 25. Component Location 2 Single Buffered Inputs in FT-22 Case; 250 Vdc. Sub 1 880A557 Figure 26. Typical External Schematic of Relay Type ARS. * Denotes change since previous issue...
  • Page 19 ARS Relay I.L. 41-759.2D *Sub 20 57D7900 Figure 27. Outline and Drilling Plan for Relay Type ARS in Ft-11 Case. * Denotes change since previous issue.
  • Page 20 *Sub 14 183A158 Figure 28. Outline and Drilling plan for Relay Type ARS in Ft-22 Case. * Denotes change since previous issue. ABB Automation, Inc. ABB Automation, Inc. Substation Automation and Protection Division Substation Automation and Protection Division 4300 Coral Ridge Drive...