Calibration To Other Instrument - CAL Controls 3300 Operating Manual

Autotune temperature controllers
Hide thumbs Also See for 3300:
Table of Contents

Advertisement

Heat Cool Strategy Configuration (continued)
If no improvement, return to the original value and;
In level 1 halve the value of
If the process hunts between heating and cooling, a
deadband setting may be needed. Enter a small value,
eg. 1 and observe the process. Increase the setting until
hunting stops.
Level 1 adjust value
Water cooled applications
Water cooled applications operating at temperatures greater
than 100°C may suffer from the non linear effect caused by
water turning to steam. This can be countered by the non
linear setting for SP2;
In level 2 set
SP2.B
Multi zone applications
When tuning multi zone applications like extruders,
distortions due to thermal interaction between adjacent
zones can be minimised by running autotune on all
controllers at the same time.
24
CYC.2
SET.2
to nL in
CALIBRATION TO ANOTHER INSTRUMENT
If the controller and instrument readings are different, the
and/or
ZERO
SPAN
Menu Level 3 will require adjustment.
Adjust
to make an equal adjustment across the
ZERO
full scale of the controller and
correction when the error increases/decreases across the
scale.
1
To adjust using the
ZERO
1.1 Substitute measured values in the expression:
Instrument reading – controller reading =
ZERO
Example:
Instrument reading = 396°
Controller reading = 400°
396 – 400
1.2 Adjust
ZERO
To make a correction when there are different
errors across the scale.
function in Function
to make a
SPAN
function
= (-)4°
to (-) 4° to correct error.