5.3
Interactive mode
5.4
Collective mode
5.5
Connection
Connection diagram interactive mode
Auxiliary supply for detector heater (option) 24V
Connection diagram collective mode
Auxiliary supply for detector heater (option) 24V
Siemens Building T
echnologies
Cerberus Division
In interactive mode the number of linear smoke detectors is limited.
Connection factor IMK = 10 for one DLO11911
In collective mode only one detector may be connected to a detector line.
Connection factor KMK = 25
+
Detector bus
–
+
–
Fig. 31 Connection diagram for interactive mode
+
Detection line
–
+
–
Fig. 32 Connection diagram for collective mode
+
–
DLB1191
«MB» = IRED pulse signal (for adjusting
+ _
+ _
the lenses during detector production)
Z MB
Y X W V
«Z» = auxiliary terminal
Line
termination
DLB1191
«MB» = IRED pulse signal (for adjusting
+ _
+ _
the lenses during detector production)
Z MB
Y X W V
«Z» = auxiliary terminal
–
+
Response indicator
–
+
Response indicator
31
e1276e