Mitsubishi Electric MUFZ-KJ-NAHZ Series Service Manual page 26

Split-type air conditioners, indoor/outdoor unit
Table of Contents

Advertisement

9-4. TROUBLESHOOTING CHECK TABLE
Before taking measures, make sure that the symptom reappears for accurate troubleshooting.
When the indoor unit has started operation and detected an abnormality of the following condition (the first detection after the
power ON), the indoor fan motor turns OFF and OPERATION INDICATOR lamp flashes.
OPERATION INDICATOR
Abnormal
No.
Operation indicator lamp
point
Left lamp flashes.
0.5-second ON
Miswiring
or serial
1
signal
0.5-second OFF
Indoor coil
Left lamp flashes.
thermistor
2-time flash
2
Room
tempera-
2.5-second OFF
ture
thermistor
Left lamp flashes.
3-time flash
Indoor fan
3
motor
2.5-second OFF
Left lamp flashes.
Indoor
4-time flash
4
control
system
2.5-second OFF
Left lamp flashes.
5-time flash
Outdoor
5
power
system
Left lamp flashes.
6-time flash
Outdoor
6
thermistors
Left lamp flashes.
7-time flash
Outdoor
7
control
system
Left lamp flashes.
14-time flash or more
Other
8
abnormality
2.5-second OFF
Outdoor
control
9
Left lamp lights up
system
Lighted
Blinking
Not lighted
Symptom
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
Indoor unit
and outdoor
unit do not
operate.
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
2.5-second OFF
Indoor unit
and outdoor
unit do not
operate.
Outdoor unit
does not
operate.
Condition
The serial signal from the outdoor unit is not
received for a maximum of 6 minutes.
The indoor coil or the room temperature
thermistor is short or open circuit.
not emitted during the indoor fan operation.
It cannot properly read data in the nonvolatile
memory of the indoor electronic control P.C.
board.
It consecutively occurs 3 times that the
compressor stops for overcurrent protection or
start-up failure protection within 1 minute after
start-up.
The outdoor thermistors short or open circuit
during the compressor operation.
It cannot properly read data in the nonvolatile
memory of the inverter P.C. board or the
outdoor electronic control P.C. board.
An abnormality other than above mentioned is
detected.
It cannot properly read data in the nonvolatile
memory of the inverter P.C. board or the
outdoor electronic control P.C. board.
26
Remedy
miswiring and serial signal
indoor coil thermistor, and the
room temperature thermistor
on 9-7.
control P.C. board.
Refer to the outdoor unit
service manual.
Refer to the outdoor unit
service manual.
board or the outdoor electronic
control P.C. board.
Refer to the outdoor unit
service manual.
detail using the failure mode
recall function.
Refer to the outdoor unit
service manual.
the LED on the inverter P.C.
board or the outdoor electronic
control P.C. board.