Mantenimiento - Beko QWIK-PURE 200 Instructions For Installation And Operation Manual

Oil water separator
Hide thumbs Also See for QWIK-PURE 200:
Table of Contents

Advertisement

Maintenance • Mantenimiento
Entretien • Manutenção
0
Fig. 1
Fig. 2
english
Weekly waste water test
• Fill test tube at the sampling valve.
• Compare the cloudiness with the refer-
ence jar.
If the sample is clearer than the reference
cloudiness
• the filter is O.K. (Fig. 1)
If the sample is cloudier than the refer-
ence cloudiness
• the filter needs to be changed!
(Fig. 2)
NOTE: Never pour any foreign liquid
into the pressure relief chamber! This
can impair the filter efficiency of the
QWIK-PURE.
Checking of level indicator
• Level indicator not visible:
- Filter condition of both stages is O.K.
• Red ring area visible:
- Main filter stage is clogged.
Replace OEKOSORB filter set!
The level indicator can be equipped with an
alarm contact as an option (page 32).
This contact switches reliably in the event
of a rising fill level inside the QWIK-PURE
unit.
• Excessive inflow quantity
• Filter clogged
• Water outlet not functioning correctly
Weekly check of leaks
• Container
• Connections
QWIK-PURE 200, 350