Parameter Values In The Display; Error List - Procon E3D 0.55 Instruction Manual

Frequency converters 0,55 – 4 kw
Table of Contents

Advertisement

F
FREQUENCY CONVERTERS INSTRUCTION MANUAL

• Parameter values in the display

• Error List

Display
Cleared
No more error in the error log. (Display in basic state)
Digital input programmed to external error
Ext.Err
activated.
L.Ph.Err
Line phase error. (at E3D series models)
Rippled
DC voltage rippled. (at E3D series models)
Current measuring error. (e.g. broken or
I Meas
shorted signal wire)
In the actual mode the motor would probably
Mot.Hot
be overheated. Probably too low frequency or
overloaded operation.
BrakeErr
Load of the brake resistor too high.
The current developed through the motor
Over Cur
exceeded the maximum value.
The DC voltage in the intermediate circuit
DC High
exceeded the permitted limit.
Hs.Hot
Heatsink temperature too high.
The IGBT module signalized error. Typical
IGBT Err
effect in case of an output short circuit.
MemWrErr
Memory writing error.
DataStE
Error in the stored data.
CHKSUM
Checksum error.
IIC Err
Internal communication error.
COM PWM
Internal communication error.
COM IO
Internal communication error.
UnknErr
Unknown error.
If the error cannot be removed with applying the troubleshooting guide and acknowledgement, contact the
manufacturer.
Row
Actual frequency
First row (fix)
Motor current
Second row
Control reference signal
The values can be
Regulation reference signal
scrolled with the
Feedback signal
 
arrows
Line voltage
DC voltage
Motor voltage
Heat sink temperature
„Total" operating hour counter
„Run" operating hour counter
Description of the error
Values
Inspect the device causing the external error.
Inspect the presence of all 3 phases.
Internal error.
Troubleshooting to be done by the manufacturer.
Effecting forced cooling, and then in menu item
65.CoolM
necessary value or decreasing the load.
Increase the run-down time in menu item
32.StopM.
Decrease the load of the motor.
With power factor corrector in front of the
appliance:
▪ insert line choke in front of the appliance.
If occurs during the stopping process:
▪ increase the run-out time in menu item
32.StopM
▪ At device equipped with built-in ventilator
checking up of its rotation beyond 45C,
▪ at device built in cabinet checking up the
ventilation of the cabinet,
▪ checking up the extent of the loading of the
device.
Checking up the wiring and connections between
the device and the motor.
After acknowledgment of the error, if the
converter is in Stop state, try to set the
parameters once again.
Disconnect the converter from the line.
If the LEDs do not light anymore, the appliance
can be restarted.
- 15 -
Short
f
Im
Cr
Rr
Fs
Ul
U+
Um
Th
O1
O2
Troubleshooting
setting the forced cooling to the